Shutdown; Cooling Unit Settings; Set Point; Local Setting - Tripp-Lite SRCOOL60KCW El Manual Del Propietario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5. Operation

5.6 Shutdown

Path: Main Menu g Power ON/ OFF g Standby
WARNING:
In standby mode, the unit is still in power-on status! You must disconnect the input power to fully power the unit
off in standby mode.
To shut down the cooling unit, first enable standby mode. After selecting standby mode, select Y, then press
STANDBY indicator displays, the unit is in the standby mode. The cooling unit is still in power-on status and the fans will be running at
the minimum speed.
Next, disconnect the external power supply. Check to make sure the fans stop and the LCD is off.

5.7 Cooling Unit Settings

5.7.1 Set Point

Path: Main Menu g Setting g Set point
y y
Supply Air T (temperature)
In automatic mode, the cooling unit will automatically adjust the fans and three-way ball valve in accordance with the set supply air
temperature.

5.7.2 Local Setting

Path: Main Menu g Setting g Local Setting
12/04/30
10:10:00
ID
:01
Contrast
:2
Buzzer
:ON
y y
System time
Use
to set up the system time, press
y y
ID (Number)
Represents the number of the cooling unit connected in series and also the ID in the Modbus protocol. The default number is 1. If
several cooling units are connected in series, you must designate each unit with a different number.
System Mode
ON
Standby
Sure?
Y/N
Supply Air T
: 25 C
Language
:
EN
User PW
:
----
Unit
:
C
Delay On
:
0Sec
to skip to the next field. Then press
29
to confirm. If the
Baud Rate
Total Alarm
to confirm.
:
9600
:
Fault
Tabla de contenido
loading

Tabla de contenido