External Piping - Tripp-Lite SRCOOL60KCW El Manual Del Propietario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3. Installation

3.7 External Piping

No.
Automatic exhaust valve
1
2
Thermometer
Ball valve
3
4
Pressure meter
Configure an external pipeline and an automatic exhaust valve
the pipeline. Set a Y-type filter
3
in front of or behind the Y-type filter to set up a branch circuit. When the filter needs cleaning or maintenance, close the ball valve to
let the chilled water go to the cooling unit via the branch to avoid shut-off loss. Install a pressure meter
filter and determine if there is a blockage according to the pressure difference.
Configure a multi-function balance valve
Pipeline flushing
To guarantee cooling efficiency, you must flush the pipeline to filter out impurities and chemical substances. For pipeline flushing, use a
hose to create a short circuit so the chilled water goes directly from the inlet end to the return end without passing through the cooling
unit. Use a fine-meshed filter (20-mesh suggested) in the Y-type filter to filter out the fine impurities. After 12 to 24 hours of water
circulation in the pipeline, change to a larger-meshed filter (3-mesh suggested).
When using a glycol additive, refer to Appendix 3: Glycol Correction Table for information about cooling capacity and water-side
pressure drop.
1
2
3
4
5
TI
PI
01
01
Inlet
Bypass
TI
02
Outlet
(Figure 3-11 : Suggested external piping)
Description
5
in the water inlet pipe to filter out impurities and chemical substances in the water. Install a ball valve
7
at the return water end for adjusting the return water flow rate.
6
7
PI
02
SRCOOL60KCW
PI
03
No.
Y-type filter
5
6
Shut-off valve
Balance valve
7
1
at the water inlet end (as shown in Figure 2-5) for removing the air in
15
Description
4
in front of and after the Y-type
Tabla de contenido
loading

Tabla de contenido