5. Operation

5.7.3 Controller Setting

Path: Main Menu g Setting g Controller
Force Mode
:
:
P Gain
I Gain
:
:
D Gain
y y
Force Mode
When force mode is enabled, the fans will run at full speed and the three-way ball valve will fully open. Force mode is generally used
for performance testing or a high heat load.
If the STANDBY indicator on the control panel flashes, the unit is in force mode. Set the proportional constant, integral constant and
derivative constant (PID). Refer to 4.7 PID Setting.
y y
Min Flow T
When the return air temperature is lower than this value, the fans will run at the minimum speed to save energy. The default is 25°C
(77°F).
y y
Max Flow T
When the return air temperature is higher than this value, the fans will run at the maximum speed. The default is 40°C (104°F).
y y
Fan Step
Sets the fan speed (range: 0~15) in automatic mode. The default is 0 and the cooling unit will adjust the fan speed according to your
setup.
y y
Auto Recover
When this function is enabled and the system is in automatic mode before powering off, the unit will directly return to the automatic
mode at restart.
y y
Intelligent
Will display if the intelligent temperature control is enabled. This option only displays the status; you cannot change the setting. To
change settings, refer to 5.7.10 Setting Automatic Control Mode.
y y
Leak Cut-Off
If this function is enabled, the unit will automatically shut down when water leakage is detected.

5.7.4 Alarm Setting

Path: Main Menu g Setting g Set Alarm
Sets Sensor Alarm, Actuator Alarm and Out-of-Range Alarm. If an item display is , this item is disabled. Press
use
to select
, and press
Note: When an alarm event occurs in manual mode, the indicator and buzzer will not activate, though the event will be stored in the event log.
OFF
Min Flow T
09.00
Max Flow T
0.550
Fan Step
0.000
Group Work
Sensor Alarm
Actuator Alarm
Out of Range
to confirm the item is enabled.
:
25 C
:
40 C
:
10
:
OFF
31
:
Auto Recover
ON
Intelligent
:
ON
:
Leak.Cut-Off
OFF
at this item,