Mounting The Wall Arm - Dräger Polaris 50 Instrucciones De Montaje Y Uso

Ocultar thumbs Ver también para Polaris 50:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 107
EN_GB
CAUTION
Take account of the wall bearing position
The wall bearing must be aligned in
accordance with the drawing
Failure to comply with correct alignment will
compromise mechanical safety
Make 4 bore hole markings
Check clearance
Drill holes, then blow them out using bellows
Use tubular dowel for the selected screws
and tighten
Wall bracket in vertical alignment, mount with
M8 self-locking bolt 1 (20 Nm / 14.75 lbf ft)
Tighten all 4 threaded pins 2 (5 Nm / 3,68 lbf
ft)
32
DANGER
Electric shocks are life-threatening.
Disconnect or remove the fuses before
working on the mains connection
Connect to mains
Push hood with ring onto the wall bracket
Connect luminaire cable
Push cover against the wall
Tighten firmly with ring
7.3

Mounting the wall arm

WARNING
The cantilever arm is an injury hazard
Do not remove the transport safeguard until
after the luminaire head has been mounted.
Loosen the screw connection and remove
the cover cap with connector
Tabla de contenido

Solución de problemas

loading

Tabla de contenido