Wiring Example - Mitsubishi Electric CITY MULTI Y Serie Manual De Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

・Wiring example
T(S)NU:
3~208–230 V
Y(S)NU: 3~460 V
L1, L2, L3
Ground
~208–230 V
L1, L2
Ground
・Be sure to use the appropriate type of circuit breaker. Note that generated overcurrent may include some amount of
direct current.
・Select the type of breaker for an inverter circuit as an earth leakage circuit breaker. (Mitsubishi Electric NV-S series
or its equivalent)
・The earth leakage circuit breaker should be used in combination with a local switch.
・Use a local switch with at least 3 mm (1/8 in) contact separation in each pole.
・Ensure the correct phase sequence. (L1, L2, and L3)
・If the power cable is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
・Use dedicated power cables for the outdoor unit and indoor unit. Ensure OC and OS are wired individually.
・Power cable size, device capacity, and system impedance
(If local regulations do not specify the minimum power cable size or device capacity, follow the values in the table
below.)
(1) TNU model
Outdoor unit model
PUHY-HP72TNU-A
PUHY-HP96TNU-A
PUHY-HP120TNU-A
PUHY-HP72TNU-A
PUHY-HP144TSNU-A
PUHY-HP72TNU-A
PUHY-HP96TNU-A
PUHY-HP192TSNU-A
PUHY-HP96TNU-A
PUHY-HP120TNU-A
PUHY-HP240TSNU-A
PUHY-HP120TNU-A
Ground
Ground
Minimum cable size
[mm
Unit combination
Power
cable
13.3 (6)
21.2 (4)
21.2 (4)
13.3 (6)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
Ground
2
(AWG)]
Earth leakage circuit breaker
Ground
55 A 30 mA or
13.3 (6)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
55 A 30 mA or
13.3 (6)
100 mA 0.1 sec. or less
55 A 30 mA or
13.3 (6)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
70 A 30 mA or
21.2 (4)
100 mA 0.1 sec. or less
Earth leakage circuit breaker
Outdoor unit
Pull box
Indoor unit
MCA (A)
(208 V/230 V)
38/35
43/40
47/43
38/35
38/35
43/40
43/40
47/43
47/43
MOP (A)
(208 V/230 V)
60/50
70/60
70/60
60/50
60/50
70/60
70/60
70/60
70/60