Precautions For Electrical Wiring - Mitsubishi Electric CITY MULTI Y Serie Manual De Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Do not purge the air using refrigerant. Use a vacuum pump to evacuate the system.
- Residual gas in the refrigerant lines will cause bursting of the pipes or an explosion.
Do not use oxygen, flammable gas, or a refrigerant containing chlorine for air-tightness
testing.
- Doing so may result in an explosion. Chlorine will deteriorate the refrigerant oil.
When installing or relocating the unit, do not allow air or any substance other than the
specified refrigerant to enter the refrigerant lines.
- Any substance other than the specified refrigerant may cause abnormally high pressure in the
refrigerant lines, resulting in bursting of the pipes or an explosion.
After the installation has been completed, check for refrigerant leaks.
- If the refrigerant leaks, oxygen starvation may result. If the leaked refrigerant comes in contact
with a heat source, toxic gas will be generated.

1-5. Precautions for electrical wiring

Include some slack in the power cables.
- Failure to do so may break or overheat the cables, resulting in smoke or fire.
Connections must be made securely and without tension on the terminals.
- Improperly connected cables may break, overheat, or cause smoke or fire.
Tighten all terminal screws to the specified torque.
- Loose screws and contact failure may result in smoke or fire.
Electrical work must be performed by qualified personnel in accordance with local
regulations and the instructions provided in this manual. Only use the specified cables and
dedicated circuits.
- Inadequate power source capacity or improper electrical work will result in electric shock,
malfunction, or fire.
Install an inverter circuit breaker on the power supply of each unit.
- Failure to do so may result in electric shock or fire.
Only use properly rated breakers (an earth leakage breaker, local switch <a switch + fuse
that meets local electrical codes>, or overcurrent breaker).
- Failure to do so may result in electric shock, malfunction, smoke, or fire.
Only use standard power cables of sufficient capacity.
- Failure to do so may result in current leakage, overheating, smoke, or fire.
Proper grounding must be provided by qualified personnel.
- Improper grounding may result in electric shock, fire, explosion, or malfunction due to electrical
noise. Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground
wires.
After the wiring work has been completed, measure the insulation resistance, and make
- Failure to do so may result in electric leakage, malfunction, or fire.
Tabla de contenido
loading

Este manual también es adecuado para:

City multi puhy-hp-tnu-aCity multi puhy-hp-ynu-a

Tabla de contenido