10 | Specifications
Q(U)
In Q(U) 10 nodes mode, the set value of the reactive power is calculated continuously as a function of
the grid voltage. This function ensures that grid support is provided by reactive power as soon as the
voltage actually deviates from the target voltage. In this case, a characteristic curve is specified which
can be used to configure up to 10 nodes, value pairs for voltage and reactive power. Other parameters
allow to limit functionality and to limit activation to certain power levels as well as parametrize the tran-
sient response.
The positive sequence voltage is used to calculate the reactive power target value for three-phase
units.
Q [%PN]
60
1) 43,6 | 207
40
20
2) 0 | 212
0
20
40
60
0
207
Fig. 48: Q(U) standard characteristic curve with 5 nodes

10.1.4 Parameters for reactive power control

Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Especific. cos-phi
1 – 0.3
Over-excited | un-
der-excited
Especific. Q
0 – 100 [% S
Under-excited |
over-excited
cos-phi(P/Plim)
Hora estab.
200 – 30000 [ms]
Tensión Lock-In
23V – 287V
Tensión Lock-Out
23V – 287V
Núm. de pu. de apoyo
2 – 10
1. punto de apoyo ...
10. punto de apoyo
Voltage | Reactive
power | Excitation
0 – 100 [% S
0 – 100%
Página 62
3) 0 | 230
4) 0 | 248
5) 43,6 | 253
230
253
Q(U) standard characteristic
Action in this menu/meaning
Specified displacement factor
Reactive power mode Under-excited relates to inductive load, over-exci-
ted relates to capacitive load.
Specification as a % of the maximum power
]
max
Reactive power mode Under-excited relates to inductive load, over-exci-
ted relates to capacitive load.
Determines the dynamic behaviour in the event of a change in the cos φ
set value. With a change of the active power or the lock-in and lock out
voltage, the cos φ is changed according to a PT-1 characteristic curve
with a settling time of 5 Tau.
The control is activated above this voltage.
The control is deactivated below this voltage.
Specify the number of nodes for the cos φ/(p/pn) characteristic curve
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
]
Note: Storage inverters only for feed-in operation
max
cos φ of the node
Manual
U[V]
Kaco blueplanet 29.0TL3