Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Tiempo muerto
1
2
3
4
4
0 s – 10 s
Rise Outg. grad. & Fall.
1
2
4
4
3
Outg. grad.
increasing | decrea-
sing
1 %-60000 %/min
1 %-60000 %/min
Cos-Phi Q1 mín. - Cos-
1
2
3
4
4
Phi Q4 mín.
Modo de prioridad
1
2
4
4
3
Q priority | P priority
Curva activa
1
2
3
4
4
1 - 4
Restablecer curva
1
2
3
4
4
Núm. de pu. de apoyo
1
2
3
4
4
2 - 10
1. punto de apoyo ...
1
2
3
4
4
10. punto de apoyo
Voltage | Reactive
power | Excitation
0 - max. voltage in
continuous operation
0-100% [% S
Over-excited | un-
der-excited
Kaco blueplanet 29.0TL3
Configuration and operation | 9
Action in this menu/meaning
F Set the intentional delay for the start of the Q(U) function.
AVISO: If the voltage switches from a characteristic curve sec-
tion with Q=0 to a characteristic curve section with Q≠0 under
active control, then the reactive power setting process is dela-
yed by the set dead time. Once the dead time has expired, the
control circuit is no longer subject to a delay and the set sett-
ling time determines the transient behaviour.
AVISO: In addition to configuring the transient behaviour
using the settling time corresponding to a first-order filter,
the reactive power setting can be determined by a maximum
gradient - maximum change in the reactive power per time
period.
F Maximum change in the reactive power %Smax/min in the event of a
change to over-excited mode.
F Maximum change in the reactive power %Smax/min in the event of a
change to under-excited mode.
AVISO: In the event of a significant voltage deviation, the ma-
ximum reactive power adjustment range can be limited by a
minimum cos φ in order to prevent an excessive reactive po-
wer supply and, as a result, a significant reduction in the maxi-
mum active power that can be fed in.
F Enter the minimum cos ϕ factor for quadrants 1 and 4.
F Set priority for reactive power – Q or active power – P.
AVISO: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cu-
rrently available and fed in.
F Select active curve.
AVISO: Up to 4 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
F Reset active curve to the default setting.
AVISO: The maximum number of configurable nodes depends
on the selected grid type.
F Specify the number of nodes for the Q(U) characteristic curve.
F Enter the voltage of the node in volts.
]
F Set the reactive power of the node as a percentage of the maximum
max
power.
F If a reactive power not equal to 1 is selected: Select the type of pha-
se shift.
Página 49