Kaco blueplanet 29.0TL3 Serie Manual página 63

Ocultar thumbs Ver también para blueplanet 29.0TL3 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Over-excited | un-
der-excited
Q(U) 10 nodes
Potencia Lock-In
0 – 100 [% S
Potencia Lock-Out
0 – 100 [% S
Hora Lock-In
0 – 60 [s]
Hora Lock-Out
0 – 60 [s]
Tiempo muerto
1
2
3
4
4
0 s – 10 s
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decrea-
sing
1 – 60000 [% S
min]
Cos-Phi Q1 mín. - Cos-
Phi Q4 mín.
Q1
Q4
Q2
Q3
Modo de prioridad
Q priority | P priority
Curva activa
1 – 4
Restablecer curva
Núm. de pu. de apoyo
2 – 10
Kaco blueplanet 29.0TL3
Action in this menu/meaning
Reactive power mode Under-excited relates to inductive load, over-exci-
ted relates to capacitive load.
Power threshold, function is activated if limit value is exceeded.
]
max
Power threshold, function is activated if limit value is undershot.
]
max
Length of time that the active power must remain below the lock-in po-
wer level before control is deactivated.
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
F Set the intentional delay for the start of the Q(U) function.
AVISO: If the voltage switches from a characteristic curve sec-
tion with Q=0 to a characteristic curve section with Q≠0 under
active control, then the reactive power setting process is dela-
yed by the set dead time. Once the dead time has expired, the
control circuit is no longer subject to a delay and the set sett-
ling time determines the transient behaviour.
In addition to configuring the dynamic behaviour using the transient ti-
me corresponding to a first-order filter, the reactive power setting can
be determined by a maximum gradient - this means the maximum chan-
ge in the reactive power per time period.
/
Maximum change in the reactive power %S
max
ge to over-excited mode
AVISO: The gradient is overlaid with the settling time.
In the event of a significant voltage deviation, the maximum reactive po-
wer adjustment range can be limited by a minimum cos φ factor in or-
der to prevent an excessive reactive power supply and, as a result, a sig-
nificant reduction in the maximum active power that can be fed in.
Minimum cos φ in over-excited operating mode (in-feed).
Minimum cos φ in under-excited operating mode (in-feed).
Minimum cos φ in over-excited operating mode (charge).
Minimum cos φ in over-excited operating mode (charge).
P priority can be selected as an alternative to the standard setting Q
priority. When it comes to P priority, the reactive power adjustment
range is limited subject to the limited apparent power of the inverter
and the active power that is currently available and fed in.
Up to four characteristic curves can be configured independently and
one of them can be activated for regulation each time.
Reset active curve to the factory setting, depending of the country set-
ting.
Specify the number of nodes for the Q(U) characteristic curve.
Specifications | 10