Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
Retardo intenc.
0 – 5000 [ms]
Frequency of the maxi-
mum deactivation th-
reshold
45 - 50.2 (Hz)
Frequency of the mini-
mum deactivation th-
reshold
45 – 50.2 (Hz)
Tiempo de desact.
0 – 3600 [s]
Grad. de desact.
0 – 65534 [% / min]
Kaco blueplanet 29.0TL3
Specifications | 10
Action in this menu/meaning
Activation threshold (f1) overfrequency:
Determines the frequency threshold for activating the function in case
of overfrequency incidents. The active power adjustment is activated if
the frequency rises above the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency falls below the
configured value.
Activation threshold (f1) underfrequency:
Determines the frequency threshold for activating the function in case
of underfrequency incidents. The active power adjustment is activated if
the frequency falls below the configured value and mode 1 or 2 is acti-
vated.
In mode 2, the function is deactivated if the frequency rises above the
configured value.
The activation of the function based on the activation threshold is dela-
yed by the configured time.
Note 1: This function is regarded as critical for the stability of the trans-
mission grid and is therefore prohibited by several national grid connec-
tion regulations.
Note 2: This function is stipulated as a requirement by some domestic
grid connection directives in order to prevent any negative impact on is-
land detection. However, P(f) has no negative impact on KACO's enhan-
ced island detection.
Deactivation range lower limit:
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation ti-
me.
Deactivation range upper limit:
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the deactivation
range and remains in this range for the duration of the deactivation ti-
me.
Only evaluated in mode 1.
The function is deactivated if the frequency returns to the range betwe-
en the minimum and maximum deactivation threshold and remains in
this range for the duration of the deactivation time.
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The li-
mitation is implemented by an absolute power limitation that increases
with a continuous gradient up to the maximum power. The actual po-
wer of the inverter may vary freely below this limit due to a possible
fluctuation in the available power or the target value, but at no time in-
creases above the absolute power limit.
Página 69