Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Parámetros de red
1
2
3
4
(further information)
BE CH-NS
Frec. desconex.
1
2
3
4
CY DE-NS
DK LU-NS
Fault Ride Through
1
2
3
4
CC Tensión inicial
1
2
3
4
Verif. protección con-
1
2
3
4
tra sobreten.
Reg. tensión const.
1
2
3
4
Kaco blueplanet 29.0TL3
Configuration and operation | 9
Action in this menu/meaning
U<<
U<
U
con,min
f<<
f<
U
con,min
If the value U< (slow undervoltage shutdown) is set to a value which is
greater than the value of U
con
display, then the value of U
con
If the value U> (slow overvoltage shutdown) is set to a value which is
smaller than the value of U
con
LC display, then the value of U
U>.
If the value f< (slow underfrequency shutdown) is set to a value which is
greater than the value of f
con
LC display, then the value of f
f<.
If the value f> (slow overfrequency shutdown) is set to a value which is
smaller than the value of f
con
LC display, then the value of f
f>.
AVISO: The device continuously monitors the grid frequency.
If the grid voltage exceeds or drops below the configured va-
lues, the device switches off.
1. Set limit values for underfrequency and overfrequency in
0.1 Hz increments.
2. Set period from occurrence of the fault to shutdown of the de-
vice.
AVISO: The device doesn't support dynamic grid stabilization
(Fault Ride-Through).
The device begins feed-in as soon as this DC voltage is present.
F Set the starting voltage.
AVISO: Please refer to the application note on our website if
you install the overvoltage protection yourself.
AVISO: Allows the monitoring of the overvoltage protection.
F Activate overvoltage protection.
AVISO: By activating, an overvoltage protection test is carried
out with an appropriate status messages
AVISO: Option to disable the MPP seek mode in order to ope-
rate the device with a constant DC voltage.
1. Activate or disable the constant voltage controller.
2. Set value for constant voltage controller.
U
U>
U>>
con,max
U
f>
f>>
con,max
,
(minimum restart voltage) using the LC
min
,
is automatically set to the value of U>.
min
,
(maximum restart voltage) using the
max.
,
is automatically set to the value of
con
max.
,
(minimum restart frequency) using the
min.
,
is automatically set to the value of
con
min.
,
(maximum restart frequency) using the
max.
,
is automatically set to the value of
con
max.