7 | Instalación
7.9.3

Ethernet connection

AVISO
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is ins-
talled. For this reason, remove the sealing insert before installation and thread the Ethernet cable out-
side of the cable fitting through the sealing insert.
AVISO
Use a suitable category 5 network cable. The maximum length of a network segment is 100 m. Ensure
that the cable is correctly assigned. The Ethernet connection of the device supports auto-sensing. You
can use both crossed and 1:1 protectively-wired Ethernet connection cables.

Conectar el cable Ethernet

↻ Cable de conexión en el interior de la unidad.
1. Conecte el cable Ethernet en uno de los dos puertos Ethernet de la placa de comunicación..
2. Coloque el cable Ethernet correctamente en la zona inferior de alimentación de CA y fíjelo con las bridas
adjuntas..
3. Apretar los prensaestopas [ W_29 /
Connecting the device to the network
↻ Connect the Ethernet cable to the device.
1. Connect the Ethernet cable to the network or a computer.
2. Configure the Ethernet settings and the web server in the Settings menu.
7.9.4

Connecting the RS485 bus

AVISO
Ensure that the DATA+ and DATA- wires are properly connected. Communication is not possible if the
wires are reversed! Different manufacturers do not always interpret the standard on which the RS485
protocol is based in the same way. Note that the wire designations (DATA- and DATA+) for wires A
and B may vary from one manufacturer to another.
1
2
A B
A B
A B
A B
A B
GND
GND
GND
GND
Fig. 37: RS485 interface wiring diagram
1 Inverter, terminal unit
2 Inverter
3 Data monitoring unit
Propiedades de la línea de datos RS485
Longitud máxima de la línea de bus RS485
Número máximo de dispositivos de bus conectados
Línea de datos
Página 32
4 Nm]
2
3
4
5
A B
GND
GND
Manual
4 Communication
5 Power supply
Max. 1200 m
Esta longitud sólo puede alcanzarse en condiciones ópti-
mas. Las longitudes de cable superiores a 500 m suelen re-
querir un repetidor o un concentrador..
99 dispositivos + 1 dispositivo de control de datos
Trenzado, apantallado.
Kaco blueplanet 29.0TL3