7.5. Adjusting the operating parameters

The menu is divided into 7 areas:
1. Control parameters: Setpoints, start/stop delays
2. Communication parameters: Field bus
3. Operating modes: Activation and deactivation of
the connected pumps
4. Information: Display of parameters currently set
as well as data for the switchgear (type, serial
number etc.)
5. Installation: Basic settings for the switchgear
6. Fault memory
7. Service
The menu structure is adapted automatically
based on the settings. Menu 1.12 is only visible if
a level sensor is connected and activated accord-
ingly in the menu.
Furthermore, the menu structure is applicable
and defi ned for all variants of the EC switchgears
(HVAC, Booster, Fire, Rain, Lift). This may lead to
gaps in numbering.

7.5.1. Menu structure

1. Start the menu by pressing the operating button
for 3 sec.
2. Follow the menu structure below for the desired
value and change this according to your specifi -
cations.
NOTICE
• Generally, values can only be displayed. Approval
must be obtained to change the values. For this,
set the value to "on" in the menu 7.01.
• If there is no operation for approx. 3 minutes,
the parameter setting is locked again!
• Some parameters can only be adjusted if no
pump is in operation.
Menu 1.00: Control parameters
No.
Description
Base-load pump stop delay
1.09
Value range: 0...60 s
Factory setting: 5 s
Peak-load pump(s) activation
delay time
1.10
Value range: 1...30 s
Factory setting: 3 s
Peak-load pump(s) stop delay
1.11
Value range: 0...30 s
Factory setting: 1 s
Base-load pump on
1.12
Value range: 0.06...12.50 *
Factory setting: 0.50 m
Base-load pump off
1.13
Value range: 0.06...12.50 *
Factory setting: 0.25 m
Peak-load pump 1 on
1.14
Value range: 0.06...12.50 *
Factory setting: 0.75 m
Peak-load pump 1 off
1.15
Value range: 0.06...12.50 *
Factory setting: 0.50 m
54
Menu 1.00: Control parameters
No.
Peak-load pump 2 on
1.16
Value range: 0.06...12.50 *
Factory setting: 1.00 m
Peak-load pump 2 off
1.17
Value range: 0.06...12.50 *
Factory setting: 0.75 m
Menu 2.00: Communication parameters
No.
ModBus On/Off
2.01
Values: off, on
Factory setting: off
ModBus: Baud rate
Values:
2.02
9600;19200;38400;76800
Factory setting: 19200
ModBus: Slave address
2.03
Value range: 1...254
Factory setting: 10
ModBus: Parity
2.04
Values: none, even, odd
Factory setting: even
ModBus: Number of stop bits
2.05
Values: 1; 2
Factory setting: 1
Menu 3.00: Operating modes
No.
Pump enabled
3.01
Values: off, on
Factory setting: off
Operating mode, pump 1
3.02
Values: off, Hand, Auto
Display
Factory setting: Auto
Operating mode, pump 2
3.03
Values: off, Hand, Auto
Factory setting: Auto
Operating mode, pump 3
3.04
Values: off, Hand, Auto
Factory setting: Auto
Menu 4.00: Information (display of current settings and
switchgear data)
No.
4.01
Current level
Current switching status of the
4.05
fl oat switches (also see Fig. 11)
Total running time of the
4.12
switchgear
4.13
Running time pump 1
OPERATION AND FUNCTION
Description
Display
Description
Display
Description
Display
Description
Display
Wilo Salmson France SAS 03-2017 V05 DIN A4