salmson Control EC-L Instalacion Y Puesta En Servicio página 65

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

APPENDIX
ModBus: Parameters
Holding register
Name
(Protocol)
40139 – 40140
Error state
(138-139)
40141
Acknowledge
(140)
40142
Alarm history index
(141)
40143
Alarm history error
(142)
code
40198
State Float switches
(197)
40204
Set points water
(203)
level 1
40205
Set points water
(204)
level 2
40206
Set points water
(205)
level 3
40212
Set points water
(211)
level 1
40213
Set points water
(212)
level 2
40214
Set points water
(213)
level 3
40220
Dry run level
(219)
40222
High water level
(221)
Installation and operating instructions Salmson-Control EC-L
Data type
Scale & unit
BITMAP32
BOOL
UINT16
UINT16
0.1
BITMAP
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
UINT16
1 cm
Elements
Access
0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
R
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communi-
cation
20: Net supply
21: Leakage
W
RW
R
0: DR
1: Ps off
2: P1 on
R
3: P2 on
4: HW
RW
RW
RW
RW
RW
RW
RW
RW
English
Added
31,000
31,000
31,000
31,000
31,102
31,102
31,102
31,102
31,102
31,102
31,102
31,102
31,102
65
Tabla de contenido
loading

Tabla de contenido