Maintenance

Safety
92
These parameters should only be changed in small increments, and
the effects on the system should be monitored continuously. Param-
eter values should only be tuned by someone with training in control
engineering.
Controller
Factory setting Setting range
term
P
0.5
I
0.5 s
D
0 s
(= deactivated)
The direction of action of the controller is determined by the sign of
the P term.
Positive PID control (default):
If the sign of the P term is positive and the process value drops below
the setpoint, the control will increase the pump speed until the set-
point has been reached.
Negative PID control:
If the sign of the P term is negative and the process value drops below
the setpoint, the control will decrease the pump speed until the set-
point has been reached.
NOTE
Check the controller's direction of action if PID control is being used,
but the pump is only running at minimum or maximum speed without
responding to changes in the parameter values.
Maintenance and repairs may only be carried out by qualified
experts!
It is recommended to have the pump serviced and checked by Salm-
sonCustomer Service.
DANGER! Risk of fatal injury!
There is a mortal danger through shock when working on electrical
equipment.
• Work on electrical equipment may only be done by electricians
approved by the local electricity supplier.
• Before working on electrical equipment, switch it off and prevent
it from being switched on again.
• Any damage to the connecting cable should always be rectified by
a qualified electrician only.
• Never use an object to poke around the openings on the module or
motor and never insert anything into the module or motor!
• Follow the installation and operating instructions for the pump,
level control device and other accessories.
Increment
-30.0 ...
-2.0
0.1
-1.99...-0.01
0.01
0.00
...
1.99
0.01
2.0
...
30.0
0.1
10 ms ... 990 ms
10 ms
1 s
... 300 s
1 s
0 ms ... 990 ms
10 ms
1 s
... 300 s
1 s