Testing The Ground Fault Sensor; Cleaning The Generator - Westinghouse PRO Serie Manual Del Propietário

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

MAINTENANCE
TESTING THE GROUND
FAULT SENSOR
1. Start the generator and allow it to warm up.
2. Press the test button on the ground fault sensor
(see Figure 62).
1
4
Figure 62 – Ground Fault Sensor Test
1 - Test Button
2 - Reset Button
3.
The light next to "fault" will light and the main
breaker will trip.
4.
If the main breaker does not trip, the ground
fault sensor is not working correctly and must be
repaired before the generator can be operated.
5.
Press the reset button and reset the main breaker.
The light next to "fault" will go out and the light next
to "power" should light. Power will be restored to all
outlets.
46
3
2
3 - Fault Light
4 - Power Light

CLEANING THE GENERATOR

It is important to inspect and clean the generator before
every use.
Clean All Engine Air Inlet and Outlet Ports – Make
sure all engine air inlet and outlet ports are clean of any
dirt and debris to ensure the engine does not run hot
(see Figure 63 and Figure 64).
Figure 63 – Engine Air Inlet and Outlet Ports – 10KPRO
Figure 64 – Engine Air Inlet and Outlet Ports – 8KPRO

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

10kpro8kpro210051210075

Tabla de contenido