ENDLESS MOTOR SHORT-
CIRCUIT.
SHORT-CIRCUIT
IN
THE
ELECTRODE
(START-UP
RESISTANCE).
LOACK OF PELLETS OR
MOTOR OBSTRUCTED.
MOTORS
OUTLET
DISCONNECTED.
CONTROL UNIT ERROR.
PROBES EXCHANGED.
AFTER THE IGNITION, THE
WATER
TEMPERATURE
INCREASES VERY FAST.
The C.P.U. detects that the reduction motor
or
tension
output
corresponding to the reduction motor is in
short-circuit.
The C.P.U.
detects that the start-up
electrode of tension output of the C.P.U.
corresponding to the electrode are in short-
circuit.
Gas outlet temperature is not sufficient for
correct functioning; the minimum must be
o
100
C.
The gas outlet sensor does not detect the
temperature required for operation.
Security thermostat activated.
The C.P.U. does not detect items of
~230/240V - 50Hz. If the boiler is new, this
might be caused by electrical problems. If it
happens after repair, it might be due to the
non connection of the motors terminal
strips.
Failure or possible failure in the C.P.U.
Gas outlet probe is exchanged by the NTC.
Air in the installation.
The Booster pump is stiff.
Installation of radiators less than 10kW.
Make sure power reaches the endless motor,
see menu 3 section 2.
Check with a multimeter if the motor is
of
the
C.P.U.
clamped to earth or the winding is in short-
circuits.
Check the blue cable going out from the
C.P.U. Connect it if necessary.
If the boiler is new, this might be caused by
electrical problems.
Check with a multimeter if the motor is
clamped to earth or the winding is in short-
circuits.
Make sure power reaches the convection
motor, see menu 3 section 3.
Check the grey cable going out from the
C.P.U. Connect it if necessary.
This is the first start-up of the boiler, wait
until the Motors stop and turn i ton again.
There were no pellets in the boiler. Fill the
hopper in.
The screw of the endless motor is
obstructed. Unblock it.
Check the quality of the pellets, see if it
contains much sawdust or humidity. Buy a
new bag of pellets.
The boiler is dirty and stopped the pellets
drop for security reasons. Carry out
maintenance.
The safety thermostat is armed. Purge the
whole heating system (see section 4) wait for
the boiler is completely cool and reset the
security thermostat.
Gas outlet sensor damaged. Replace it.
C.P.U. damaged. Replace it.
Disconnect the Test of Control of the
hardware in menu 1-7b, disconnect the
boiler and connect it again; if everything
works well, tension decreases or you hear
noise in the electric mains.
Check with a multimeter that the motors are
not in short-circuits.
Disconnect the Test of Control of the
hardware in menu 1-7b, disconnect the
boiler and connect it again; if everything
works well, tension decreases or you hear
noise in the electric mains.
The thermocouple and NTC are exchanged,
see wiring diagram.
Purge installation, boiler and booster pump.
Unstiff the pump (see point 4).
Increase the installation.
44