Initial start-up
7.10 Analysing refrigerant
NOTE
I
The AirConServiceCenter analyses the purity level of the refrigerant before
draining. If it is below 98.5%, the unit does not accept the refrigerant.
Each time before draining the vehicle or filling the internal refrigerant ves-
sel, the refrigerant analysis starts automatically.
If "Please wait" is flashing, the refrigerant is being analysed.
7.10.1 Refrigerant analysis passed
If the refrigerant is not contaminated, the AirCon Service Center displays
the following at the end of the analysis:
The AirConServiceCenter can be used.
7.10.2 Refrigerant analysis failed
If the refrigerant fails the analysis, the AirConServiceCenter displays the
following:
1. Confirm "Try again" with ENTER.
The AirConServiceCenter checks up to three times. If the third analysis is
still not successful, the AirConServiceCenter displays the following:
84
Refrigerant analysis
Warm up
Please wait!
Refrigerant analysis
Please wait!
STOP-EXIT
Refrigerant analysis
OK!
Refrigerant analysis
Refrigerant not OK
Try again?
ENTER-OK
Refrigerant analysis
not OK.
Take the unit
out of operation!
AirConServiceCenter
No
EN