How to dispose of the instrument
This maintenance schedule is intended for guidance only. The actual level of
maintenance required will depend on the severity of the operating environment
and the likelihood of damage or the rate of contamination from oil, sea spray,
deluge system etc. It is advisable to regularly review maintenance reports and
adapt the maintenance period to the operating environment.
Proof Testing
Proof testing should be carried out on a yearly basis. Probability of failure on
demand per year for SIL2 capable devices must be 10
1. By-pass/inhibit the safety function and take appropriate action to avoid a
false trip.
2. Clean the detector window using a soft cloth and a detergent.
3. Test the detector using a Dräger FS-5000 flame simulator.
4. Remove the by-pass/inhibit and restore normal operation.
Personnel carrying out commissioning, testing and maintenance on this device
shall be sufficiently competent and experienced to do so.
6
How to dispose of the instrument
This product must not be disposed of as household waste. This is indi-
cated by the adjacent symbol.
You can return this product to Dräger free of charge. For information
please contact the national marketing organizations or Dräger.
7
Technical data
Temperature
-60 ° to +85 °C (-76 to +185 °F)
Humidity
5-95 % relative humidity
IP rating
IP 66, NEMA 4X
Supply voltage
18 to 32 VDC (nominal 24 VDC)
Power consumption
6 W (max. 15 W with heater)
CE marking
Devices and protective systems for the use for the
intended purpose in explosion-hazard area (Direc-
tive 2014/34/EU)
14
Dimensions
Cable entries
Weight
Aluminium housing
Stainless steel housing
-3
-2
to 10
.
Regulatory approvals
ATEX
IECEx
FM
SIL2
Reliability
Mean time between fail-
ure (MTBF)
Response time
220 × 100 mm (7.9" × 3.9" inches)
M20, M25 or 3/4" NPT
2.5 kg (5.5 lbs)
6 kg (13.2 lbs)
Certificate number: FM21ATEX0078
II 2 G Ex db IIC T4
Certificate number: IECEx FME 21.0005
Ex IIC T4
Class I, Div 1, Groups B, C, D, T4
Ambient: -60 ° to +85 °C (-76 to +185 °F)
Class I, Zone 1, AEx/Ex db IIC T4
Ambient: -60 ° to +85 °C (-76 to +185 °F)
FM approved acc.
FM 3260 "Radiant Engery-Sensing Fire Detectors
for Automatic Fire Alarm Signaling"
Certificate number: DR 0905050 C001,
IEC 61508:2010 Parts 1-7
348,530 hours
Approximately 7 seconds (maximum 30 seconds)