TEST RUN MENU
Element
Optional function
Prevention of low air
outlet temperature in
cooling mode
Models:
RPI-(4.0-6.0)FSN5E
RPIM-(0.6-1.5)FSN4E(-
DU)
d4
Not used
Models:
RCD-FSN3
RPI-(0.4-3.0)FSN5E
RPI-FSN3E(P)E(-f)
RCI-FSN4
RPC-FSN3
RCIM-FSN4E
RPF(I)-FSN2E
RPI-(8~20)FSN3(P)E
Prevention of low air
outlet temperature in
d5
heating mode
Room temperature
d6
control for energy saving
Econofresh: Minimum
opening angle of the
d7
outdoor air (OA) damper
KPI: Ventilation mode
E1
Econofresh cooling
mode
14
PMML0496 rev.1 - 12/2020
Individual
Settings
setting
Function disabled
00
(factory setting)
O
01
00
O
-
01
Function disabled
00
(factory setting)
O
Function enabled
01
Function disabled
00
(factory setting)
O
01
6º (factory setting)
00
12º
01
18º
02
24º
03
O
30º
04
36º
05
42º
06
48º
07
Automatic ventilation
00
(factory setting)
Ventilation with total heat exchanger
01
Ventilation with bypass (no total
02
heat exchange)
O
Standard process
00
(factory setting)
All Fresh
01/02
Setting conditions
This function is used to prevent
the decrease of discharge air
temperature in cooling operation, by
controlling thermo ON/OFF according
to the discharge air temperature.
When ambient temperature > setting
temperature:
If air outlet temperature ≤ 11 ºC for
3 minutes, the system is switched to
Function enabled
Thermo-OFF.
In this status, if air outlet temperature
≥ 13 ºC, the system is switched back
to Thermo-ON.
Use at 00 conditions
This function prevents the occurrence
of an excessively cold air flow in
heating mode by decreasing the fan
speed during heating operation, also
taking into account the setting of
function C5..
This function saves energy when the
outdoor temperature is lower than the
air conditioning load.
The indoor unit is set to cooling
Thermo-OFF when
Function activated
Tout (outside ambient temperature -
out of the building) < Tin
This function is used to set the
minimum opening angle of the
damper for fresh outdoor air.
This function allows the outdoor air
damper to be opened in All Fresh
operation mode. This mode allows
the full opening of the outdoor air
damper (according to the control
system).
This function allows the outdoor air
damper to be opened in All Fresh
operation mode. This mode allows
to fully open the outdoor air damper
(according to the control system).