MENU OPERATION
4 Press " " or " " and select the setting function. The setting
will change as follows:
"Control" ↔ "LOW" ↔ "MED" ↔ "HIGH".
Capacity Control
OK
/
?
5 Press "
" or "
" and select setting content.
If "Control" is selected, it will change as follows:
-
"Peak Cut Control" ↔ "Moderate Control".
If "LOW, MED or HIGH" is selected, it will change as
-
follows:
"100%" ↔ "90%" ↔ "80%" ↔ "70%" ↔ "60%" ↔ "50%"
↔ "40%" ↔ "0%".
Press "OK" after completing all settings.
The next setting screen will be displayed.
OK
Capacity Control
/
?
OK
/
?
6 By pressing "
" or "
", the setting function will change as
follows
"LOW→MED→HIGH" ↔ "LOW Only" ↔ "MED Only" ↔
"HIGH Only".
Press "OK" after completing the setting.
Capacity Control
OK
/
?
OK
/
?
46
PMML0496 rev.1 - 12/2020
Control
Peak Cut Control
100%
LOW
80%
MED
60%
HIGH
Operate in power set value range.
Sel.
Adj.
OK
Entr
Control
Peak Cut Control
100%
LOW
80%
MED
60%
HIGH
Operate in power set value range.
OK
Sel.
Adj.
Entr
Chg level
LOW MED HIGH
Select setting range of
power saving.
OK
Adj.
Entr
7 The confirmation screen will be displayed. Select "Yes" by
pressing "
The screen will return to the normal mode.
If the power saving setting is available, set it "ON" using the
"Power Save Guide".
OK
Rtrn
OK
8.5.2 Power saving detailed setting (Indoor unit
rotation control)
This function sets the parameters of the indoor unit rotation
control.
Control Method
"Sort by Adress": Indoor units are set to FAN mode
depending on their H-LINK address, in ascending order, one
by one.
"Sort by Temperature difference": Indoor units are set
to Fan mode according to the temperature difference
between temperature set point and air inlet temperature, in
ascending order: units for which TSet is closer to the setting
temperature are the first to be switched to fan mode.
Rtrn
"Sort by Absence:*" If the motion sensor is used, Fan mode
will be applied to the indoor unit that has the lowest activity
detected. Once the fan mode operation time is elapsed, this
unit returns to the previous operation mode and fan mode is
applied to another indoor unit with the lowest activity.
*: This function can only be set with outdoor units and indoor
units supporting it.
FAN Operation Time
It is possible to change the timing of the FAN operation of the
indoor unit.
?
N O T E
The "Main/Sub-Remote" display in "9.1 Current Setting" in the "9 Help
Rtrn
Menu" cannot be set if the indication is "Sub" or "−−".
If the "Power Saving Mode" changes, the power saving "Detailed
Setting" in the outdoor unit capacity control, "Power Saving ON/OFF"
will be OFF.
This function can only be used when the operation mode is COOL
or HEAT.
The cooling/heating capacity can decrease when using the "Power
Saving" function.
" or "
", and press "OK" to confirm the setting.
Power Saving Mode Setting
/
?
Fix power saving settings.
Cancel current power saving
settings?
Yes
/
?
Sel.
No
OK
Entr
Rtrn