Over temperature
in the power
section
E04
(LED Fault)
Flashes once (LED
Ready) On
Electronic motor
overload
E05
(LED Overload)
Flashing
TM 514 – COMMON RAIL TEST
When the heatsink
temperature is superior
to the limit.
Also trips when the
temperature sensor is
not connected.
When the times given
by the programmed
thermal class curves
exceed the limit.
177
Shaft load too high.
Elevated number of
successive starts.
Internal temperature
sensor not connected.
Starting cycle requires
ventilation kit (models
from 45 A to 200 A).
Incorrect setting of the
"Motor Current"
trimpot (motor current
set).
The set value is too
low for the motor
being used.
Starting sequence
greater than allowed.
Programmed thermal
class too low.
Time between Off/On
procedures lower than
that permitted by the
motor power
refrigeration time.
Load on the motor
shaft too high.
Thermal protection
value saved when the
control is turned off
and brought back
when turned back on.
Power-on.
Reset key.
Auto-reset.
DIx.
Power-on.
Reset key.
Auto-reset.
DIx.