7.7.8. FOOD PROBE ALARM ===> CONTACT TECHNICAL ASSISTANCE
The food probe is used for reading core temperature in blast chill cycles.
A fault in the food probe causes an alarm only if a set temperature blast chill cycle is in progress.
In this case the cycle automatically coverts the setting to time and the buzzer (optional) is activated.
Alarm code ER2 will fl ash on DISPLAY 1.
The buzzer (optional) sounds, but can be stopped by pressing the button.
The alarm code display disappears by pressing a button.
FOOD PROBE ALLARM:
7.7.9. EVAPORATOR PROBE ALARM ===> CONTACT TECHNICAL ASSISTANCE
The probe allows termination of defrosting based on temperature.
Press and release button
DISPLAY 2.
If the probe is defective, an evaporator probe alarm and buzzer are activated, and error code ER3
fl ashes on the display.
The buzzer (optional) sounds but can be stopped by pressing a button.
Once the fault is remedied, the alarm cancels automatically.
With the probe alarm on, defrosting terminates in time.

7.8. HACCP

When the HACCP symbol fl ashes, it means that a new HACCP alarm has occurred.
In order to view the alarm, access HACCP alarm display by pressing the HACCP button
Display1 indicates the alarm type 'AL1'
Display2 indicates 'A L'
Display3 indicates the position of alarm '4'
The HACCP symbol lights up.
If the alarm is for High/Low temperature, the thermometer symbol
If the alarm is for Time-Out or Blackout, the clock symbol
The illustration indicates that the last alarm was for high temperature and 4 is the position in the
alarm memory. 10 HACCP alarms can be memorised and allocated to positions 0 to 9.
The UP and DOWN buttons can be used to scroll through the memorised alarms.
Press button
Display1 indicates the day on which alarm '15' started
Display2 indicates 'dd'
Display3 indicates the alarm number '4'
Pressing the botton
'15'
'd d'
where 'tt' indicates the duration of the alarm in minutes.
If the alarm is for low or high temperature, the display after the date is the minimum or maximum
temperature reached:
Display1 indicates maximum temperature '-10'
Display2 indicates 'H t' or 'L t"
Press button
to view the date of alarm start:
or
'10'
'05'
'14'
'M M'
'y y'
'h h'
to exit from the alarm start date view and return to view the alarms.
1
, to see the temperature of the evaporator which is shown on
to view the date and time:
'45'
'127'
'm m'
't t'
2
3
lights up.
lights up.
29 - GB
4
.