8. LCD Display and Settings
3. Output Setup
Route: Main Screen Setting OUTPUT SETUP
VOLT (V): The UPS system's output voltage when in Normal (Online) Mode. There are three voltage settings: 220, 230 and 240V. The
default setting is 230V.
FREQ (HZ): The UPS system's output frequency when in Normal (Online) Mode. There are two frequency settings: 50 or 60 Hz. The
default setting is 50 Hz.
FREQ CONVERTER: Enables or disables the Frequency Converter. The default setting is OFF.
ECO: Enables or disables ECO Mode. The default setting is OFF.
REDUNDANCY (UNIT): The number of redundancy units in a configuration. There are 5 settings: 0, 1, 2, 3 and 4. The default setting is 0.
INDUSTRIAL: When connecting to a non-linear load with a high inrush current, the user can switch to this mode until the output current
recovers. The default setting is OFF.
Use function keys (
), (
4. Charger Setup
Route: Main Screen Setting CHARGER SETUP
CHARGE CURRENT: The charge current range is 1.0~5.0. The default setting is 2.0.
CHARGE FLOAT VOLT(V): Sets the floating voltage. The default setting is 272.
CHARGE BOOST VOLT(V): Sets the boost voltage. The default setting is 280.
BOOST CHARGE TIME (HOURS): There are four settings: 04, 08, 12, 16, 20 and 24. The default setting is 08.
AUTO BOOST CHARGE PERIOD: There are four settings: OFF, 1M, 3M, 6M. The default setting is OFF.
Use function keys (
), (
) and (
) to change the OUTPUT SETUP setting.
) and (
) to change the CHARGER SETUP setting.
41