8. LCD Display and Settings
5. Battery Setup
Route: Main Screen  Setting  BATTERY SETUP
BAT RATING VOLT (V): The default setting is 240.
TYPE (AH): Sets the battery rating. The default setting is 18.
LOW BATTERY ALARM (220): The default setting is 220.
SHUTDOWN VOLT (V): The default setting is 192V.
BATTERY NUMBER: The default setting is 20.
Install Date (Y-M-D): Battery's actual install date.
Replace Date (Y-M-D): Battery's replacement date.
Use function keys (
), (

6. Battery Test

Route: Main Screen  Setting  BATTERY TEST
Auto Deep Discharge: There are four settings: OFF, 30D, 60D and 90D. The default setting is OFF.
Manual Test: Initiates the start of a battery manual test. The test time is five minutes. If the battery's voltage is lower than 220V, the
result is fail. If above, the result is pass.
Clear Test Result: Clears the battery test result.
Use function keys (
), (
) and (
) to change the BATTERY SETUP setting.
) and (
) to change or initiate the BATTERY TEST setting.