Tripp-Lite SmartOnline SUTX20K Manual Del Propietário página 35

Sistema ups trifásico 20/40kva, entrada - 220/230/240v fase - neutro 380/400/415v fase - fase, 3ph 4 hilos + tierra física
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Communication Interfaces
No.
Event
Battery cabinet over
12
temperature warning/
shutdown
13
Abnormal inverter voltage
14
Battery needs replacement
Bypass over temperature
15
warning/shutdown
16
Bypass static switch fail
17
Over temperature fail
18
General alarm
6
Input Dry Contacts
The UPS provides two sets of input dry contacts that are open by default. The default setting for Pin 1 and 2 is "ROO" and the
default setting for Pins 3 and 4 is "Generator Power Supply Signal". There are two configuration types:
Figure 6-6 shows the first type of input dry contact configuration. It requires internal power, +12VSF.
Figure 6-7 shows the second type of input dry contact configuration. It requires external power with a voltage range between
6~12V DC.
Description
The external battery cabinet's temperature is too high.
The output voltage is too high or too low.
Battery replacement date is due.
Bypass static switch temperature is too high.
The bypass static switch has open/short issue.
The UPS temperature is out of range.
When any of above-mentioned events occurs.
Pin 1
Pin 2
(Figure 6-5: Input Dry Contacts)
6
1
4
3
GS
1
6
3
4
GS
UPS
(Figure 6-6: Input Dry Contact Configuration I)
6
1
4
3
GS
1
6
3
4
GS
UPS
(Figure 6-7: Input Dry Contact Configuration II)
P1 P2
Pin 4
Pin 3
2K(1206)
2K(1206)
1
2
3
+12VSF
4
2K(1206)
2K(1206)
2K(1206)
2K(1206)
1
2
3
+12VSF
4
2K(1206)
2K(1206)
35
+
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Smartonline sutx40k

Tabla de contenido