Tripp-Lite SmartOnline SUTX20K Manual Del Propietário página 19

Sistema ups trifásico 20/40kva, entrada - 220/230/240v fase - neutro 380/400/415v fase - fase, 3ph 4 hilos + tierra física
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3. Installation and Wiring
2
After removing the panels, use the following method to modify the UPS from single input into dual input.
Remove the four cables that connect the AC input terminal block and the bypass breaker (see Figures 3-7 and 3-8). When wiring,
connect the bypass source's R, S, T and N cables to the bypass breaker.
(Figure 3-15: Remove the Four Cables that Connect the AC Input Terminal Block and the Bypass Breaker)
Dual Input (Parallel Units)
When there are two AC power sources, parallel units' wiring procedures are as follows:
1
Follow 3.6.4 Dual Input Modification to modify the UPS into dual input. Only authorized Tripp Lite engineers or service personnel
can modify single input/dual input setup.
2
Follow steps
1
~
5
3
Connect the main AC source/ bypass AC source/output/external battery cabinet cables to the wiring terminal block. Do not forget to
ground the parallel UPS systems (refer to Figures 3-13~3-18/3-20).
4
Use the provided parallel cable to connect the parallel ports on the parallel units. See Figure 6-1 for parallel port location.
5
Refer to 6. Communication Interfaces to set the parallel switch in the ON or OFF position.
6
Follow step
7
in section 3.6.2 Single Unit Wiring.
WARNING:
1. When UPS systems are paralleled, the length of each unit's input cables/output cables must be equal. This
ensures that the parallel UPS systems will equally share the equipment loads in bypass mode.
2. Only UPS systems with the same capacity, voltage and frequency may be paralleled; otherwise, parallel function
is forbidden.
3. Before start-up of parallel units, qualified service personnel should set ID (0, 1, 2 or 3) through the LCD.
Otherwise, UPS systems cannot be started. If the symbol '!' appears after an ID number, it indicates there is a
conflict between ID numbers.
SUTX20K
(20kVA Model)
I
ON
I
ON
I
ON
I
ON
I
ON
I
ON
I
ON
I
ON
O
OFF
O
OFF
O
OFF
O
OFF
O
OFF
O
OFF
O
OFF
O
OFF
R
S
T
N
R
S
T
N
INPUT BREAKER
BYPASS BREAKER
-
+
N
R
S
T
N
AC INPUT
240V DC
240V DC
BATTERY INPUT
SUTX40K
(40kVA Model)
I
ON
I
ON
I
ON
I
ON
I
ON
I
ON
OFF
OFF
OFF
OFF
OFF
OFF
O
O
O
O
O
O
R
S
T
N
R
S
INPUT BREAKER
BYPASS BREAKER
-
+
N
R
S
T
AC INPUT
240V DC
240V DC
BATTERY INPUT
in section Single Input (Single Unit).
Remove the
four cables
R
S
T
N
UPS OUTPUT
I
ON
I
ON
OFF
OFF
O
O
T
N
Remove the
four cables
N
R
S
T
N
UPS OUTPUT
19
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Smartonline sutx40k

Tabla de contenido