Low Calibration Point
Distance from Sensor Reference Point to Low
Calibration Point: usually process empty level.
Range: 0.000 to 40.000 m or
0.000 to 100.000 m
Values
Default: 40.000 or 100.000 m
High Calibration Point
Distance from Sensor Reference Point to High
Calibration Point: usually process full level.
Range: 0.000 to 40.000 m or
0.000 to 100.000 m
Values
Default: 0.000 m
Wizard Complete
BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wizard menu when Quick
Options
Start is successfully completed.)
To transfer Quick Start values to the device and return to Program menu, press
Then press
to return to Measurement mode.
SITRANS LR560 Communications: PROFIBUS PA
Notes:
• The following instructions assume that the user is familiar with PROFIBUS PA.
• You will need the full manual to acquire the list of applicable parameters.
• Application Guides for setting up PROFIBUS PA devices with SIMATIC PDM can be down-
loaded from the product page of our website at: www.siemens.com/LR560. Go to Support
> Software Downloads.
Configuring the PROFIBUS PA master
To configure SITRANS LR560 on the network, you will need the GSD file SIEM816B.gsd. You
can download the file from the product page of our web site at: www.siemens.com/LR560. Go
to Support > Software Downloads.
SIMATIC PDM
We recommend that you use SIMATIC Process Device Manager (PDM) to program your
device. Please consult the operating instructions or online help for details on using
SIMATIC PDM. You can find more information at www.siemens.com/simatic-pdm.
Check the support page of our website to make sure you have the latest version of SIMATIC
PDM, the most recent Service Pack (SP) and the most recent hot fix (HF). Go to:
https://support.automation.siemens.com/WW/
llisapi.dll?func=cslib.csinfo&lang=en&siteid=csius&aktprim=0&extranet=standard&view
reg=WW&objid=10806857&treeLang=en
A5E32043113
SITRANS LR560 (PROFIBUS PA)
(Finish).
Page EN-13