Configuring a new device
: Clicking on Cancel during an upload from device to SIMATIC PDM will result in some
Note
parameters being updated.
1)
Check that you have the most recent EDD, and if necessary update it (see
Electronic Device Description (EDD)
2)
Launch SIMATIC PDM and create a new project for LR200.
3)
Open the menu Device – Master Reset and click on OK to perform a reset to Factory
Defaults.
4)
After the reset is complete upload parameters to the PC/PG.
5)
Configure the device via the Quick Start wizard (see below).
Quick Start Wizard via SIMATIC PDM
Notes:
• The Quick Start wizard settings are inter-related and changes apply only after you click on
FINISH AND DOWNLOAD at the end of step 5 to save settings offline and transfer them to
the device.
• Click on BACK to return and revise a setting or Cancel to exit the Quick Start.
Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 5.
Operating via FDT (Field Device Tool)
FDT is a standard used in several software packages designed to commission and maintain
field devices. Two commercially available FDTs are PACTware and Fieldcare.
To configure a field device via FDT you need the DTM (Device Type Manager) for the device.
Siemens instruments use SITRANS DTM and an instrument EDD written for SITRANS DTM.
1) First install SITRANS DTM on your system. You can download it from:
http://support.automation.siemens.com. Click on Product Support, and navigate to Product
Information/Automation Technology/Sensor systems/Process Instrumentation/Software &
Communications.
2) Install the SITRANS LR200 HART EDD for SITRANS DTM. You can download it from the
product page of our website at: www.siemens.com/LR200. Go to Support > Software
Downloads.
Configuring a new device via FDT
An Application Guide can be downloaded from the product page of our website under Support.
Page EN-20
SITRANS LR200 (HART) – QUICK START MANUAL
on page 19.
Quick Start