System components
– Dräger Pulsar 7x00
Future Dräger transmitters with HART
Technical data
Number of input channels: 2 or 4
Transmitter supply volt-
age:
Transmitter supply cur-
rent:
Signal input current range: 0 to 24 mA (short-circuit detection at 38 mA)
Input resistance:
Measurement accuracy:
Current consumption:
Power loss:
Measured value update
rate:
Monitoring functions:
4.2.2
Relay Module 4/8 Ch
Output module in 2 versions with 4 or 8 independent relay outputs for switching
24 V DC and 240 V AC mains power loads.
112
®
communication are also supported.
Typically 24 V, depending on the supply voltage of the
Docking Station
Max. 500 mA per channel
Total transmitter supply current per module:
2 Ports max. 1 A
4 Ports max. 2 A
If 1 A or 2 A is exceeded, the transmitters require an
external power supply.
At ambient temperatures <50 °C, the max. transmitter
supply current per module is 2 A.
262 ohm
± 0.05 mA ±0.002 mA/K [0 ... 4 mA]
± 1.25 % ±0.05%/K [4 ... 24 mA]
Max. 2.1 A
Max. 5 W at 24 V
1 s
– wire break detection (loop current < 0.1 mA)
– Fault detection (loop current > 38 mA; this value
should be included when calculating the maximum
line resistances)
– Short circuit detection (transmitter supply current >
500 mA; channel shuts down if this is exceeded)
– Total current monitoring (sum of transmitter supply
currents on all channels > 2,000 mA; module shuts
down if this is exceeded)
Instructions for use
|
REGARD 3000