GE G60 Manual De Instrucciones página 606

Tabla de contenido
B.4 MAPA DE MEMORIA
Tabla B–9: MAPA DE MEMORIA DE MODBUS (Hoja 41 de 60)
DIR
NOMBRE DE REGISTRO
A732
...Repetido para Non-Volatile Latch 6
A73C
...Repetido para Non-Volatile Latch 7
A746
...Repetido para Non-Volatile Latch 8
A750
...Repetido para Non-Volatile Latch 9
A75A
...Repetido para Non-Volatile Latch 10
B
A764
...Repetido para Non-Volatile Latch 11
A76E
...Repetido para Non-Volatile Latch 12
A778
...Repetido para Non-Volatile Latch 13
A782
...Repetido para Non-Volatile Latch 14
A78C
...Repetido para Non-Volatile Latch 15
A796
...Repetido para Non-Volatile Latch 16
Digital Counter (configuración de lectura/escritura) (8 módulos)
A800
Digital Counter 1 Function
A801
Digital Counter 1 Name
A807
Digital Counter 1 Units
A80A
Digital Counter 1 Block
A80B
Digital Counter 1 Up
A80C
Digital Counter 1 Down
A80D
Digital Counter 1 Preset
A80F
Digital Counter 1 Compare
A811
Digital Counter 1 Reset
A812
Digital Counter 1 Freeze/Reset
A813
Digital Counter 1 Freeze/Count
A814
Digital Counter 1 Set To Preset
A815
Reservado (11 elementos)
A820
...Repetido para contador digital 2
A840
...Repetido para contador digital 3
A860
...Repetido para contador digital 4
A880
...Repetido para contador digital 5
A8A0
...Repetido para contador digital 6
A8C0
...Repetido para contador digital 7
A8E0
...Repetido para contador digital 8
Frequency Rate of Change (configuración de lectura/escritura) (4 módulos)
A900
Frequency Rate of Change 1 Function
A901
Frequency Rate of Change 1 OC Supervision
A902
Frequency Rate of Change 1 Min
A903
Frequency Rate of Change 1 Max
A904
Frequency Rate of Change 1 Pickup Delay
A905
Frequency Rate of Change 1 Reset Delay
A906
Frequency Rate of Change 1 Block
A907
Frequency Rate of Change 1 Target
A908
Frequency Rate of Change 1 Events
A909
Frequency Rate of Change 1 Source
A90A
Frequency Rate of Change 1 Trend
A90B
Frequency Rate of Change 1 Pickup
A90C
Frequency Rate of Change 1 OV Supervision
A90D
Frequency Rate of Change 1 Reserved (3 elementos)
A910
...Repetido para Frequency Rate of Change 2
A920
...Repetido para Frequency Rate of Change 3
A930
...Repetido para Frequency Rate of Change 4
Restricted Ground Fault (configuración agrupada de lectura/escritura) (6 módulos)
A960
Restricted Ground Fault 1 Function
B-50
RANGO
0 a 1
---
---
0 a 65535
0 a 65535
0 a 65535
–2147483647 a
2147483647
–2147483647 a
2147483647
0 a 65535
0 a 65535
0 a 65535
0 a 65535
---
0 a 1
0 a 30
20 to 80
20 to 80
0 a 65.535
0 a 65.535
0 a 65535
0 a 2
0 a 1
0 a 5
0 a 2
0.1 a 15
0.1 to 3
0 a 1
0 a 1
Sistema de protección de generador G60
UNIDADES
PASO
FORMATO
---
1
F102
---
---
F205
---
---
F206
---
1
F300
---
1
F300
---
1
F300
---
1
F004
---
1
F004
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
---
1
F102
pu
0.001
F001
Hz
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F224
Hz/s
0.01
F001
pu
0.001
F001
---
1
F001
---
1
F102
APÉNDICE B
PREDETERMINADO
0 (Desactivado)
"Counter 1"
(ninguno)
0
0
0
0
0
0
0
0
0
0
0 (Desactivado)
200
4500
6500
0
0
0
0 (restablecimiento
automático)
0 (Desactivado)
0 (SRC 1)
0 (Increasing)
50
700
0
0 (Desactivado)
GE Multilin

Hide quick links:

Tabla de contenido
loading

Tabla de contenido