GE G60 Manual De Instrucciones página 185

Tabla de contenido
5 CONFIGURACIÓN
E) PROTOCOLO DNP
PATH: SETTINGS
PRODUCT SETUP
 DNP PROTOCOL
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
MENSAJE
GE Multilin


COMMUNICATIONS
DNP PROTOCOL
 DNP CHANNELS
DNP ADDRESS:
65519
 DNP NETWORK
 CLIENT ADDRESSES
DNP TCP/UDP PORT
NUMBER: 20000
DNP UNSOL RESPONSE
FUNCTION: Disabled
DNP UNSOL RESPONSE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MAX RETRIES: 10
DNP UNSOL RESPONSE
DEST ADDRESS: 1
DNP CURRENT SCALE
FACTOR: 1
DNP VOLTAGE SCALE
FACTOR: 1
DNP POWER SCALE
FACTOR: 1
DNP ENERGY SCALE
FACTOR: 1
DNP PF SCALE
FACTOR: 1
DNP OTHER SCALE
FACTOR: 1
DNP CURRENT DEFAULT
DEADBAND: 30000
DNP VOLTAGE DEFAULT
DEADBAND: 30000
DNP POWER DEFAULT
DEADBAND: 30000
DNP ENERGY DEFAULT
DEADBAND: 30000
DNP PF DEFAULT
DEADBAND: 30000
DNP OTHER DEFAULT
DEADBAND: 30000
DNP TIME SYNC IIN
PERIOD: 1.440 min
Sistema de protección de generador G60
5.2 CONFIGURACIÓN DEL PRODUCTO
Rango: vea el submenú abajo
Rango: 0 a 65519 en pasos de 1
Rango: vea el submenú abajo
Rango: 1 a 65535 en pasos de 1
Rango: Enabled, Disabled
Rango: 0 a 60 s en pasos de 1
Rango: 1 a 255 en pasos de 1
Rango: 0 a 65519 en pasos de 1
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Rango: 0 a 100000000 en pasos de 1
Rango: 0 a 100000000 en pasos de 1
Rango: 0 a 100000000 en pasos de 1
Rango: 0 a 100000000 en pasos de 1
Rango: 0 a 100000000 en pasos de 1
Rango: 0 a 100000000 en pasos de 1
Rango: 1 a 10080 min en pasos de 1
5