Connecting

3.6 Sensor Wiring

2. Slide sensor into a mounting frame back end first aligning the angled edge of the sensor
with the angled edge of the mounting frame. Keep sensor from making contact with the
pipe until it butts up against the mounting frame stop. Push sensor down to mate with
pipe.
3. Tighten the sensor clamping screws to hold the sensor firmly in place.
for the other sensor.
3.6
Sensor Wiring
3.6.1

Wiring the Sensors

Connecting Sensors to the Transmitter
1. Open the transmitter top cover. Using a flat blade screwdriver, remove the Cable Strain
Relief bracket (see figure below).
2. Observing the upstream and downstream orientation, attach the UP (upstream) and DN
(downstream) cables to the sensors and make snug. Attach the other ends to the UP and
DN terminals of the flow meter (see figure below).
3. Replace the Cable Strain Relief bracket. Close top cover.
4. Proceed to Commissioning (Page 47).
44
Repeat procedure
FUG1010 IP65 NEMA 4X Quick Start
Operating Instructions, 06/2014, A5E02951527-AC