SITRANS LR 400 Wiring Requirements
•
All field wiring must have insulation suitable for the applied input voltage
•
4-20 mA, Profibus-PA, dc input circuits, 14-20 AWG, shielded copper wire
•
ac input circuit, minimum 14 AWG copper wire
•
Recommended torque on terminal clamping screws, 0.5-0.6 Nm
•
The 24 Vdc version must only be connected to SELV or PELV circuits.