Mounting location

Recommendations
• Easy access for viewing the display and programming via the hand programmer.
• An environment suitable to the housing rating and materials of construction.
Precautions
• Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to
variable frequency motor speed controllers.
• Avoid interference to the emission cone from obstructions or from the fill path.
• Avoid central locations on vessels.
Coni
Conical
preferred
Locate the antenna away from the side wall, to
avoid interference from indirect echoes.
Avoid interference from objects such as ladders
or pipes, which can cause false reflections.
Avoid interference from the fill path.
s.
To provide optimum signal conditions on a manhole cover, locate the antenna off-center
relative to the cover, typically 100 mm (4") from the side of the manhole.
Use the 100 mm (4") shield on nozzles that are 100 mm (4") in length, or shorter.
Use the 250 mm (10") shield on nozzles that are 250 mm (10") in length, or shorter.
Page EN-4
SITRANS LR 200 – QUICK START MANUAL
Fl
at
Flat
Parabolic
undesirable
minimum
100 mm (4")
min. 300 mm (1 ft.) for every
3 m (10 ft.) of vessel height
beam
angle
o
20
minimum
10 mm (0.4")
7ML19985QL81