Plumbing system connection
The connection of the stove to the
plumbing system must be made
ONLY by specialized personnel
who are capable of carrying out installa-
tion properly, in compliance with current
standards in the country of installation.
The manufacturer will not be held respon-
sible for damage to persons or things in
the event of failed operation if the afore-
mentioned warning is not complied with.
There are 2 different types of systems:
- Closed vessel system
- Open vessel system.
Closed vessel system
This product has been designed and built to
work with closed vessel systems. In general, the
closed vessel system has the following expan-
sion as the expansion vessel pre-loaded. In ad-
dition to the expansion device, the closed ves-
sel system must be provided in accordance with
current Italian UNI 10412-2 (2009) by:
•
safety valve
•
thermostat control of the circulator
•
device alarm sounds
•
temperature Indicator
•
pressure indicator
•
audio alarm
•
automatic adjustment
•
safety thermostat with manual reset
•
circulation system
Open vessel system
The open vessel system is a more secure system
that does not require the addition of further se-
curities. The fireplace stoves, wood boilers and
stoves necessarily require use of an open ves-
sel
system.
A plant run open vessel, connected
to a thermoproduct, may provide for circulator
mounted on the return, in this way the system
would work at lower temperatures to the advan-
tage of a longer
life.
While working under optimal
conditions, the pump mounted on the back can
push the water through the tube pan on safety
and can make it back in the system through the
inlet pipe causing a phenomenon of oxygen that
is highly damaging to life of the boiler.
To prevent this phenomenon, it is possible to ap-
ply the following measures:
•
lower the speed of the pump so as to reduce
the prevalence
•
hold, if possible, the tray a little lower and raise
the maximum allowed the safety tube
•
perform the separation between the safety
pipe and the discharge pipe, not at an angle of
90 ° but with a curved connection.
Diagram connection kit without hot water
thermostove
A 2
WATER
RETURN
C
The pressure relief valve (C) must always be
connected to a water drain pipe. The tube must
be capable of withstanding high temperature
and pressure.
Directions for use
If the installation of the thermostove provides
interaction
with
another
complete with a heater (gas boiler, gas boiler, oil
A 1
WATER
DELIVERY
existing
system