12
Spare parts
13
Factory settings
Installation and operating instructions Ixens, Ixens Bloc
Spare parts may be ordered via a local specialist and/or Samson cus-
tomer service.
When ordering spare parts, make sure to state all the information
given on the pump and drive rating plates (for the pump rating plate,
see Fig. 11, Item 1, for the drive rating plate, see Fig. 12, Item 3). This
helps prevent return queries and incorrect orders.
CAUTION! Risk of property damage!
Trouble-free pump operation can only be guaranteed when origi-
nal spare parts are used.
• Only use original Salmson spare parts.
• Each component is identified in the table below.
• Information to be provided when ordering spare parts:
• Spare part number
• Name/description of the spare part
• All data on the pump and drive rating plates
NOTE:
For a list of original spare parts, see the Salmson spare parts docu-
mentation (www.salmson.com). The item numbers on the exploded
view drawing (Fig. 7) are intended as orientation and to provide a list
of the pump components (see list "Tab. 2: Arrangement of the main
components" on page 76). These item numbers are not to be used to
order spare parts.
For the factory settings, see Tab. 13 below.
Menu
Designation
no.
1.0.0.0 Setpoints
2.0.0.0 Control mode
3.0.0.0 Δp-v gradient
2.3.3.0 Pump
4.3.1.0 Base-load pump
5.1.1.0 Operating mode
5.1.3.2 Internal/external pump
cycling
5.1.3.3 Pump cycling time interval
5.1.4.0 Pump enabled/disabled
5.1.5.0 SSM
5.1.6.0 SBM
5.1.7.0 External off
5.3.2.0 IN1 (value range)
5.4.1.0 IN2 active/inactive
5.4.2.0 IN2 (value range)
5.5.0.0 PID parameter
5.6.1.0 HV/AC
5.6.2.0 Emergency operation speed
5.6.3.0 Auto reset time
5.7.1.0 Display orientation
5.7.2.0 Pressure value correction
English
Factory-configured values
• Controller:
approx. 60 % of n
pump
max
• Δp-c:
approx. 50 % of H
pump
max
• Δp-v:
approx. 50 % of H
pump
max
Δp-c activated
Lowest value
ON
MA
Main/standby operation
Internal
24 h
Enabled
Collective fault signal
Collective run signal
Collective external off
0–10 V active
OFF
0–10 V
See chapter 9.4 "Setting the con-
trol mode" on page 110
HV
approx. 60 % of n
pump
max
300 s
Display on original orientation
Active
127