Δp
Pump 1
Fig. 21: Pump cycling
Behaviour of the inputs and outputs
Fault and run signals
Operating possibilities at the slave
pump
Installation and operating instructions Ixens, Ixens Bloc
Pump 2
• Pump 1 turns (black line)
• Pump 2 is switched on at minimum speed and soon afterwards
• Pump 1 is switched off
t
• Pump 2 continues to run until the next pump cycling
• At the master: acts on the whole unit
• Set at the master (menu <5.1.7.0>): depending on the setting in menu
• Set at the slave: acts only on the slave
• A collective fault signal (SSM) can be connected to the master for a
• In this case, the contact may only be made to the master.
• The display is for the whole unit.
• This signal can be programmed on the master (or using the IR-Moni-
• The contact must be made to each pump for individual fault signals.
• A collective run signal (SBM) can be connected to the master for a
• In this case, the contact may only be made to the master.
• The display is for the whole unit.
• This signal can be programmed on the master (or using the IR-Moni-
• The functions – "Readiness", "Operation", "Mains on" – from EBM/
• The contact must be made to each pump for individual run signals.
Manual or external pump cycling is possible five seconds after the last
pump cycling, at the earliest.
Activation of external pump cycling simultaneously deactivates
internal time-controlled pump cycling.
Pump cycling can be described schematically as follows (see also
Fig. 21):
reaches the setpoint (grey line)
NOTE:
In manual control mode, a slight increase in flow can be expected.
Pump cycling is depending on the ramp time and generally lasts 2 s. In
auto control, there may be minor fluctuations in the delivery head.
However, pump 1 adjusts itself to the changed conditions. Pump
cycling is dependent on the ramp time and generally lasts 4 s.
Actual value input IN1 setpoint input IN2
"External off":
<5.1.7.0>, acts only on the master or on the master and the slave
ESM/SSM:
central control centre.
tor/IR-Stick) as an individual fault signal (ESM) or a collective fault
signal (SSM) in menu <5.1.5.0>.
EBM/SBM:
central control centre.
tor/IR-Stick) as an individual fault signal (ESM) or collective fault sig-
nal (SSM) (menu <5.1.6.0>).
SBM can be set at <5.7.6.0> on the master.
NOTE:
"Readiness" means:
The pump could run, there is no fault.
"Operation" means:
Motor turning.
"Mains on" means:
Mains voltage is present.
The only settings that are possible at the slave are "External Off" and
"Disable/enable pump".
NOTE:
If an individual motor is switched voltage-free in a double pump, the
integrated dual pump management is deactivated.