CI500 / CI750 Blower Motor
PROBLEMS
Belt Slips
Belt Breaks
Belt Jumps Sheave Grooves
Belt Cracking
Belt Wearing Rapidly

Status LED's - Heat Mode

PROBLEMS
Power, Thermostat, and High Limit LED
are ON
The power and thermostat LEDs are ON,
but the burner motor does not start
Only the Power LED is ON
Power, Thermostat, and Main Motor LED
are ON, but blower motor will not operate
Foreman Ductable Dual Fuel Indirect-Fired Heater
CAUSE
Pulleys worn (Belts bottoming
out in grooves)
Oil or grease on belt
Improper belt installation. Belt
pried over pulleys using sharp
or pointed tools.
Drive misaligned
Dirt entering pulleys
Dirt or grease on belt or aged
belt
Worn pulleys
Dirt in pulleys
Check both high limit switches. Reset or replace.
The air pressure switch is in the closed position
(CI230).
Defective burner motor or capacitor
Burner wheel fan binding
If a thermostat is connected, ensure the set point on
the thermostat is above room temperature.
If a thermostat is not connected, check the thermostat
toggle switch is set to MANUAL.
Blower fan motor defective, replace motor
Faulty heater controller
Bad relay
Fan wheel binding
Owner's Manual • Foreman
SOLUTION
Replace pulleys
Clean pulleys or belt
Install new belt properly
Check and realign
Remove belt, clean the pulleys
Remove dirt or replace belt
Replace pulleys
Remove dirt