baltur BT 75 DSPG Manual De Mantenimiento, Uso E Instalación página 12

Ocultar thumbs Ver también para BT 75 DSPG:
Tabla de contenido
FUEL FEEDING HYDRAULIC DIAGRAM FOR ONE OR MORE LIGHT OIL BURNERS
E
WITH MAXIMUM NOMINAL VISCOSITY (5 °E at 50 °C) FROM 75 TO 300 DSPG
N
G
1
Main cictern
2
Filter
L
3
Circulation pump
I
4
Water and system drain
S
6
Fuel recovery and degasifier
7
One-way valve
H
8
By-pass (usually closed)
9
Feeding circuit presure regulator
adjustment range between 0.2 and 1 bar
10 Pressure gauge (0 - 4 bar)
The combustible recovery and degasifier tanks (diameter ~ 150, height ~ 400) should be installed as near as possible to the burner
and should be about 0,5 m. higher with respect to the burner's pump.
DIAGRAM OF PIPES OF FEED SYSTEM FOR LIGHT OIL BURNERS WITH MAXIMUM
NOMINAL VISCOSITY (5 °E at 50 °C)
1
Main cictern
2
Filter
3
Circulation pumps
4
Water and system drain
5
Air-gas drain usually closed
6
Fuel recovery and degasifier
7
One-way valve
8
By-pass (usually closed)
The combustible recovery and degasifier tanks (diameter ~ 150, height ~ 400) should be installed as near as possible to the
burner and should be about 0,5 m. higher with respect to the burner's pump.
12 / 32
98319_200910
N° 0002901120
rev.: 19/02/2002
N° BT 8666/3