Operating instructions
•
20 mA output current calibration (mode 3b)
−
In mode 3b, the measurement range start at 20.00 ± 0.01 mA is set at the out-
put
−
Pressing the M button briefly takes you back to mode 3a (the settings for
4 mA and 20 mA are entirely independent of each other - this means checking
or recalibration is necessary).
−
Press the M button for a longer period to put the unit back into measuring
mode (mode 1)
Reset to default setting (mode 3k)
Once the correct password (110) has been input, use the M button to go to mode 3k.
Procedure:
•
If you simultaneously press the
from modes 4 to 12 are reset to the default setting, as is the output current setting
(modes 3a and 3b), and the unit goes automatically into measuring mode
(mode 1)
•
If you press the M button, the unit will go into measuring mode (mode 1) without
being reset to default settings
SITRANS P, ZD series
A5E00249308-01
Servicing and maintenance
↑
↓
button and the
button, the unit's parameters
61