UM_s-MEXT_ME28relC_00_12_19_ML
2.4.2.
Main loop mask table
Press [UP] or [DOWN] to move from one mask to another.
Below are the main loop masks
Mask of the terminal
1
ACTIVE FUNCTIONS
DELAY FOR TIME
OBSERVATION
2
24.0 °C
35.0 °C
3
AUXILIARY T-H PROBE
Addr. 129
24.0 °C
50.0 %
Status:Offline
4
REQUEST STATUS
Cooling request: 100%
Step request:
Waiting:
5
PAC-IF013B-E MASTER
Active step:
Mode:
Status:Online
6
PAC-IF013B-E SLAVE1
Active step:
Mode:
Status:Online
7
0 08.0bar
03.3°C
USER MANUAL
Description of the mask
Mask that displays the active functions of the unit
Visible only when certain functions are active
15.0 °C
Active probe value display mask
Room temperature probe
Temperature probe
Mask that displays the value of the serial auxiliary probe (address 129).
Visible if the probe is configured
Mask displaying the requests of cold and steps sent to the PCA-IF013B-E card
It also shows if the system is waiting for the expiry of a time delay before sending the steps to the
Master PAC-IF013B-E card:
•
[NONE]
11
•
[SHORT WAIT]
NONE
•
[LONG WAIT]
•
[CHANGING MODE]
•
[MIN T.OFF]
Master PAC-IF013B-E status
Pressing [ENTER] will take to the section containing additional Master PAC-IF card information
11
In case of alarm, the
COOLING
code from the PAC-IF card. For additional information on the meaning of the code, see the "Event
Mask" chapter.
Slave 1 PAC-IF013B-E status
Pressing [ENTER] will take to the section containing additional Slave 1 PAC-IF card information
11
In case of alarm, the
COOLING
code from the PAC-IF card. For additional information on the meaning of the code, see the "Event
Mask" chapter.
08.0bar
Mask for the display of the values of the active probes and their conversions into temperature
03.3°C
•
Circuit 1 low pressure switch
•
Circuit 2 low pressure switch
Delivery temperature probe
No delay
Short delay (300s / 5min)
Long delay (600s / 10min)
Cycle inversion/mode change (120 s / 2min)
Minimum Off (120s / 2min)
icon will flash showing the "PAC-IF code:" message followed by the alarm
icon will flash showing the "PAC-IF code:" message followed by the alarm
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
35