ELECTRICAL AND CONTROL SETTINGS
8. ELECTRICAL AND CONTROL SETTINGS
8.1
General check
• Make sure that the following conditions related to
power supply installation are satisfied:
✓ The power capacity of the electrical installation
is large enough to support the power demand
of the YUTAKI system (outdoor unit + DHW tank
(if apply)).
✓ The power supply voltage is within ±10% of the
rated voltage.
✓ The impedance of the power supply line is low
enough to avoid any voltage drop of more than
15% of the rated voltage.
• Following the Council Directive 2004/108/EC, relating
to electromagnetic compatibility, the table below
indicates the Maximum permitted system impedance
Z
at the interface point of the user's supply, in
max
accordance with EN61000-3-11.
Power
Model
supply
~ 230 V
RASM-(4-6)VR1E
50 HzV
50Hz
3N~ 400V
RASM-(4-7)R1E
50Hz
~ 230 V
RASM-(4-6)VRW1E
50 HzV
50Hz
3N~ 400V
RASM-(4-7)RW1E
50Hz

NOTE
(*)Only for RASM-(4-7)(V)R1E: The data corresponding to DHW tank
heater is calculated in combination with the domestic hot water
tank accessory "DHWT-(200/300)S-3.0H2E".
• The status of Harmonics for each model, regarding
compliance with IEC 61000-3-2 and IEC 61000-3-12,
is as follows:
Status regarding compliance
with IEC 61000-3-2 and
IEC 61000-3-12
Equipment complying with IEC
61000-3-2
(*): Professional use
Equipment complying with IEC
61000-3-12
PMML0578 rev.0 - 04/2022
• Check to ensure that existing installation (mains
• When install RASM-(V)R1E with DHW tank
8.2
The electrical wiring connection for the outdoor unit is
shown in figure below
Z
Operation
max
(Ω)
-
0.26
With DHWT
0.17
-
-
With DHWT
0.28
-
0.26
-
-
Models
RASM-(4-7)R(W)1E
RASM-(4-6)VR(W)1E
Status regarding compliance
with IEC 61000-3-2 and
IEC 61000-3-12
Installation restrictions may be
applied by supply authorities in
relation to harmonics
power switches, circuit breakers, wires, connectors
and wire terminals) already complies with the
national and local regulations.
(DHWT-(200/300)S-3.0H2E), set in PCB1 the DSW4
pin3 ON (factory setting OFF) if DHK tank heater is
required.
Electrical Wiring Connection for Outdoor
Units
RASM-(4-6)VR(W)1E
Power supply
1~ 230V 50Hz
RASM-(4-7)R(W)1E
Power supply
3N~ 400V 50 Hz
Models
-
Control cable
(5V)
Control cable
(5V)
9
EN