5. Design guidelines
5. Design guidelines
The installation and all connections must
conform to the relevant standards and
regulations!
5.A. Burner location requirements
The distance of boiler walls and accessories from the room
walls must guarantee easy and fault free operation of the hot
water boiler (boiler control system operation, effi cient manual
fuel feeding to the storage hopper, repairs, inspections etc.).
Ensure suffi cient space when planning and installing the boiler
and its accessories in the distance required to open all boiler
doors, clean the combustion chamber and the exchanger
baffl es. The following diagram (see 'Boiler location in the
boiler room - dimension diagram') and the table (see 'Boiler
dimension data') shows recommended installation space for
the boiler and its accessories.
Table 'Boiler room dimension data'
Boiler room dimensions
Marking
A1
B1
C1
H1
g
Experts in heating
unit
Values
mm
≥ 500
mm
≥ 700
mm
≥ 500
mm
≥ 2000
mm
≥50
Fig. Boiler location in the boiler room – dimension diagram