Mitsubishi Electric Mr.Slim PLA-A-BA4 Manual De Instalación página 3

Idiomas disponibles

Idiomas disponibles

. Installation location
Refer to the outdoor unit installation manual.
3. Installing the indoor unit
Fig. 3-1
25/32 to 1-25/32
33-27/32 to 35-13/16
6-5/16
7-3/8
Fig. 3-2
2-3/8 11-3/16
14-27/32
A12, A18, A24, A30
A36, A42
Fig. 3-3
37-3/8
25/32 to 1-25/32
31-7/8
6-5/16
33-1/16
Min. 19-11/16
(mm, inch)
A
B
Models
80, 3-5/32
74, 2-29/32
85, 3-11/32
77, 3-1/32
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
Accessory name
Installation template
Washers (with insulation)
Washers (without insulation)
Pipe cover (for refrigerant piping joint)
Small diameter
Large diameter
Band
Screw with washer (M5 × 25) for mounting grille
Drain socket
Insulation
3.. Ceiling openings and suspension bolt installation
(inch)
locations (Fig. 3-)
Caution:
Install the indoor unit at least 2.4m (94-1/2inch) above floor or grade level.
For appliances not accessible to the general public.
• Using the installation template (top of the package) and the gauge (supplied as
an accessory with the grille), make an opening in the ceiling so that the main unit
can be installed as shown in the diagram. (The method for using the template
and the gauge is shown.)
* Before using, check the dimensions of template and gauge, because they
change due to fluctuations of temperature and humidity.
* The dimensions of ceiling opening can be regulated within the range shown
in Fig.3-2; so center the main unit against the opening of ceiling, ensuring
that the respective opposite sides on all sides of the clearance between them
becomes identical.
• Use M10 (3/8") suspension bolts.
* Suspension bolts are to be procured at the field.
• Install securely, ensuring that there is no clearance between the ceiling panel &
grille, and between the main unit & grille.
Outer side of main unit
A
Bolt pitch
B
Ceiling opening
C
Outer side of Grille
D
* Note that the space between ceiling panel of the unit and ceiling slab, etc. must be 10 to 15 mm,
25/64 to 19/32 inch.
When the optional multi-functional casement is installed, add 135 mm,
*
5-5/16 inch to the dimensions marked on the figure.
Models
A12, A18, A24, A30
A36, A42
3.3. Refrigerant and drainage piping locations of
indoor unit
The figure marked with * in the drawing represent the dimensions of the main unit
excluding those of the optional multi function casement. (Fig. 3-3)
Drain pipe
A
Ceiling
B
Grille
C
Refrigerant pipe (liquid)
D
Refrigerant pipe (gas)
E
Water supply inlet
F
Main unit
G
When the optional multi-functional casement is installed, add 135 mm, 5-5/16inch
*
to the dimensions marked on the figure.
Q'ty
1
4
4
1
1
8
4
1
1
Grille
E
Ceiling
F
Multi function casement (option)
G
Entire periphery
H
(mm, inch)
C
D
241, 9-1/2"
258, 10-3/16"
281, 11-1/16"
298, 11-3/4"
3
loading