3.3.3 Configuring pool cover mode
The pool cover mode is used to adapt the dehumidifier and heating functions to the pool status (covered/not covered).
When the pool cover is detected as closed, the heating setpoint temperature switches to the (lower) setpoint defined
in setting "P66" (see § 3.4.3 "Configuring setpoint temperatures").
This setting helps to reduce energy consumption during periods when no one is swimming.
Uncovered
Setpoint T (°C) = 28°C / "P07"
This example shows the temperature setpoint automatically switching from "P07" = 28°C to "P66" = 20°C when the
pool is covered.
To activate or deactivate this function you will have to:
1. First connect the pool cover switch (see §2.6.1 "Terminal block detail");
2. Set the pool cover mode to enabled:
• In the "EASY" menu, browse with the
confirm.
• Using the
or
- Yes = activate the pool cover mode (default setting).
- No = deactivate the pool cover mode.
• Press
key to confirm.
OK
• Press
key a number of times to go back to the previous screens.
When the pool cover mode is enabled and activated and the machine detects such input and the symbol
in the screen.
3.3.4 Setting the RTC (Real Time Clock)
The appliance uses an internal clock (RTC) to keep track of time, thus enabling a feature described in §3.4.5 "Time
bands". To achieve this, the user must be sure that the date and time shown in the appliance is correct. Otherwise, the
RTC has to be adjusted as show below.
To set the RTC, enter in the RTC section, present in the menu screen 2, (see § 3.3 "Appliance configuration" for
reference).
or
keys until you reach the "P67" setting, then press
keys, select:
• Press
OK
• Use
• Then press
• Contnue the process until the date and time are correct.
• Press
OK
• Press
Setpoint T (°C) = 20°C / "P66"
, the two date digits will be highlighted.
and
keys to set the correct number.
key to move to the month digits.
to confirm.
to go back to previous screens.
Covered
OK
to
is shown