1.3 I Technical specifications
DF2 - (without kits)
Voltage
Protection class
Pollution degree
Overvoltage category
Nominal electric current requirement
Maximum electric current requirement
Minimum cable section
Dehumidifying capacity
Power input
2
Power input
maximum
2
Air flow ("Standard" mode)
Available head loss (inlet + outlet)
Acoustic power
Ducted
Approximate weight
Through the wall
Refrigerant gas
Refrigerant gas load
Refrigerant gas service pressure
(max / min)
Service temperature (max / min)
Protection rating
"Electrical heater" kit: Power = 4.500 W
Power
Nominal electric current requirement
"Electrical heater" kit: Power = 9.000 W
Power
Nominal electric current requirement
Hot water coil" kit: inlet water temperature at 70 °C minimum / 90 °C maximum.
Power
Water flow
Head loss
Maximum water pressure
"Hot water coil" kit: inlet water temperature at 40 °C minimum / 50 °C maximum.
Power
Water flow
Head loss
Maximum water pressure
"Hot water coil" kit: inlet water temperature at 70 °C minimum / 90 °C maximum.
Power
Water flow
Head loss
Maximum water pressure
"Hot water coil" kit: inlet water temperature at 40 °C minimum / 50 °C maximum.
Power
Water flow
Head loss
Maximum water pressure
Values provided as a guide only for a maximum length of 20 metres, these must be verified and adjusted to suit the installation requirements and
1
the installation standards of the country.
Model without options, under the following nominal conditions: air 30°C, humidity 70%.
2
10
Top view: Main components
03M
A
7,9
A
15
mm²
3x2,5
1
3G2,5
L/h
3,5
2
W
1 755
3 278
m³/h
1.300
Pa
db(A)
71,5
113
kg
121
kg
1,4
TeqCO
2,92
2
bar
MPa
°C
W
A
W
A
W
m³/h
kPa
bar/kPa
W
m³/h
kPa
bar/kPa
W
m³/h
kPa
bar/kPa
W
m³/h
kPa
bar/kPa
05M
08M
10M
220 - 240V / 1 N~/ 50 Hz
11,9
16,6
21,5
19,2
29,1
34,2
3x4,0
3x6,0
3x10,0
3G4,0
3G6,0
3G10,0
5,6
8,7
10,7
2 580
3 560
4 620
4 195
6 358
7 473
1.300
1.700
2.000
71,5
73,6
75
114
117
147
122
125
155
R410A
1,5
1,75
2,56
3,13
3,65
5,33
42 / 12
4.2 / 1.2
65 / -16
4.500
20,5
NA
NA
14,33
16,86
23,26
0,64
0,75
1,03
16,2
21,9
20,6
6/600
4,53
5,30
7,41
0,39
0,46
0,65
14,7
10
13,4
6/600
14,86
17,81
22,23
0,66
0,79
0,99
16,9
23,6
18,6
6/600
4,74
5,65
7,07
0,41
0,49
0,62
15,0
11,0
11,8
6/600
05T
08T
10T
380 - 400V/ 3 N~/ 50 Hz
I
2
II
4,3
6,03
8,5
7,9
14,5
15,5
5x2,5
5G2,5
5,6
8,7
10,7
2 510
3 514
4 609
4 647
8 529
9 117
1.300
1.700
2.000
200
71,5
73,6
75
114
117
147
122
125
155
1,5
1,75
2,56
3,13
3,65
5,33
IPX4
6,8
NA
9.000
NA
13,7
14,33
16,86
23,2
0,64
0,75
1,03
16,2
21,9
20,6
4,53
5,3
7,41
0,39
0,46
0,65
14,7
10
13.4
14,86
17,81
22,23
0,66
0,79
0,99
16,9
23,6
18,6
4,74
5,65
7,07
0,41
0,49
0,62
15
11
11,8
12T
9
17,5
5x4,0
5G4,0
12,1
4 999
10 294
76,7
149
157