Air Pressure Switch; Ionization Current - baltur BTG 3 Manual De Instrucciones

Quemadores de gas de una etapa
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

generaL DIagram for reDUCIng tHe Lpg preSSUre to tWo StepS for BUrner or BoILer
Pressure gauge and pressure intake
1st step reducer
Output ~30 mbar
Flow rate ~ double
t h e m a x i m u m
required by the
user
2nd step reducer
Tank
Output ~ 30 mbar
L.P.G.
Flow rate ~ double the maximum

aIr preSSUre SWItCH

Regulate the air pressure switch after first carrying out all the other
burner adjustments with the air pressure switch adjusted to the start
of the scale. With the burner operating at the requested power level,
slowly turn the central screw clockwise until the burner locks out.
Then give the screw a half-turn anti-clockwise and repeat burner
start-up to check for proper operation. If the burner locks out again
give the knob another half-turn.

IonIZatIon CUrrent

The minimum current needed to run the apparatus is 3µA.
The burner provides a significantly higher current and therefore
does not normally require any checks at all. Should however, the
ionisation current need to be measured a microammeter must be
connected in series to the ionization electrode lead by opening the
connector "C" as illustrated in the figure.
2nd step reducer
Output ~ 30 mbar
Flow rate ~ double the maximum required by the user
Filter (steam type)
Pressure intake
Filter (steam type)
required by the user
19 / 22
0006080742_201306
Filter
Vibration-proof joint
Ball cock
Filter
Freestanding or wall-mounted boiler
Burner