cecotec ENERGYSILENCE 12000 AIR CLIMA CONNECTED Manual De Instrucciones página 37

Ocultar thumbs Ver también para ENERGYSILENCE 12000 AIR CLIMA CONNECTED:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
ENGLISH
Tool
Mini vacuum pump
Filling device
Concentration detector
Pressure gauge
70
ENERGYSILENCE 12000 AIR CLIMA CONNECTED
Requirement for use
It should be an explosion-proof vacuum pump;
can ensure certain precision and its vacuum
degree should be lower than 10 Pa.
It should be a special explosion-proof filling
device; have certain precision and its filling
deviation should be less than 5 g.
The maintenance site should be equipped
with a fixed-type combustible refrigerant
concentration detector and connected to a
safeguard alarm system; its error must be not
more than 5%.
The installation site should be equipped
with a portable combustible refrigerant
concentration detector which can realize
two-level audible and visual alarm; its error
must be not more than 10%.
The
concentration
detectors
should
calibrated regularly.
It is necessary to check and confirm the
functions before using the concentration
detectors.
The pressure gauges should be calibrated
regularly.
The pressure gauge used for Refrigerant 22
can be used for Refrigerants R290 and R161;
the pressure gauge used for R410A can be
used for Refrigerant 32.
Fire extinguisher
Indoor unit installation
Note:
The purchaser must ensure that the person and/or company who is to install, maintain or
repair this air conditioner has qualifications and experience in refrigerant products. It must be
a authorized installer or company.
Install the indoor unit on a strong wall that is not subject to vibrations.
The inlet and outlet ports should not be obstructed: the air should be able to blow all over the
room.
Do not install the unit near a source of heat, steam, or flammable gas.
Install the unit near an electric socket or private circuit.
be
Do not install the unit where it will be exposed to direct sunlight.
Select a site where the condensed water can be easily drained out, and where it is easily
connected to outdoor unit.
Check the machine operation regularly and reserve the necessary spaces as shown in the
picture.
Select a place where the filter can be easily taken out.
Fig.7.
1.
Mounting plate
2. Condensed water drain pipe
3. Sleeve
4. Insulating covering
5. Electrical cable
6. Water drain pipe
Installation diagram
Fig. 8.
1.
Outdoor unit
2. Indoor unit
Installation of the mounting plate
Fig. 9.
ENGLISH
It is necessary to carry fire extinguisher(s)
when installing and maintaining an air
conditioner. On the maintenance site, there
should be two or more kinds of dry powder,
carbon dioxide and foam fire extinguishers and
that such fire extinguishers should be placed
at stipulated positions, with eye-catching
labels and in handy places.
ENERGYSILENCE 12000 AIR CLIMA CONNECTED
71

Hide quick links:

Tabla de contenido
loading

Tabla de contenido