4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 20 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation it is sufficient to press the RESET button (part 8 - fig. 1) for 1 second or use
the RESET on the remote timer control (optional) if installed;if the boiler does not restart
it is necessary to resolve the fault first.
Other faults cause temporary shutdowns (marked with the letter "F") that are automati-
cally reset as soon as the value in question returns to within the boiler's normal working
range.
Table of faults
Table. 3 - List of faults
Fault
Fault
Possible cause
code
No gas
Ignition/detection electrode fault
A01
No burner ignition
Faulty gas valve
Insufficient gas supply pressure
Trap blocked
Faulty ignition transformer
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature
A03
protection activation
No water circulation in the system Check the circulating pump
Air in the system
Fume extraction duct
Fault F07 generated 3 times in the
A04
safety device activation
last 24 hours
Fault F15 generated for 1 hour
A05
Fan protection activated
(consecutive)
Ionisation electrode fault
Flame unstable
No flame after ignition
Gas valve Offset fault
A06
stage
(6 times in 4 minutes)
air/fume ducts obstructed
Trap blocked
Flue partially obstructed or
insufficient
F07
High fume temperature
Fume sensor position
Sensor damaged
F10
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Sensor damaged
F11
Return sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F12
DHW sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F13
Fume sensor fault
Wiring shorted
Wiring disconnected
Sensor damaged
F14
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
No 230V power supply
F15
Fan fault
Tachometric signal interrupted
Fan damaged
Supply voltage under
F34
Electric mains trouble
170V
F35
Faulty mains frequency
Electric mains trouble
Pressure switch contact
F37
Low system pressure
open
Probe damaged or wiring shorted Check the wiring or replace the sensor
F39
External probe fault
Probe disconnected after
activating the sliding temperature
60
EN
Cure
Check the regular gas flow to the boiler
and that the air has been eliminated from
the pipes
Check the wiring of the electrode and that
it is correctly positioned and free of any
deposits
Check the gas valve and replace it if
necessary
Check the gas supply pressure
Check the trap and clean it if necessary
Check and replace it if necessary
Check the ionisation electrode wiring
Check the card
Check the correct positioning and
operation of the heating sensor
Vent the system
See fault F07
See fault F15
Check the position of the ionisation
electrode and replace it if necessary
Check the burner
Check the Offset adjustment at minimum
power
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Check the trap and clean it if necessary
Check the efficiency of the flue, fume
extraction ducts and outlet terminal
Check the correct positioning and
operation of the fume sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the 3-pin connector wiring
Check the 5-pin connector wiring
Check the fan
Check the electrical system
Check the electrical system
Check the system water pressure
Reconnect the external probe or disable
the sliding temperature
cod. 3541A282 - Rev. 01 - 02/2013
Fault
Fault
Possible cause
code
Delivery sensor disconnected from
A41
Sensor positioning
the pipe
A42
Heating sensor fault
Sensor damaged
Sensor damaged
Cascade temperature sen-
F50
Wiring shorted
sor fault
Wiring disconnected
F52
Heating sensor fault
Sensor damaged
A61
Controller DBM27 fault
Controller DBM27 internal error
No communication
Controller not connected
A62
between controller and
Valve damaged
gas valve
A63
A64
Controller DBM27 fault
Controller DBM27 internal error
A65
F66
5. TECHNICAL DATA AND CHARACTERISTICS
Key of figures cap. 5
7
Gas inlet
Model 125 = 1"
Model 220 = 1"
Model 320 = 1" 1/4
10
System delivery
16
Fan
32
Heating circulating pump (not supplied)
36
Automatic air vent
44
Gas valve
67
Ignition transformer
72
Room thermostat (not supplied)
72b
Second room thermostat (not supplied)
81
Ignition electrode
82
Detection electrode
95
Diverter valve (not supplied)
A = Heating phase
B = DHW phase
C = Neutral
NOTE: For valves with 2 wires and spring return, use the connections B and C
98
Switch
114
Water pressure switch
130
DHW circulating pump (not supplied)
138
External probe (not supplied)
139
Remote timer control (not supplied)
154
Condensate drain pipe
155
Hot water tank temperature probe (not supplied)
186
Return sensor
191
Fume temperature sensor
220
Ignition card
275
Heating system drain cock
278
Double sensor (Safety + Heating)
298
Cascade temperature sensor (not supplied)
299
Input 0-10 Vdc
300
Burner lit contact (voltage-free contact)
301
Fault contact (voltage-free contact)
302
Remote reset input (230 Volt)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
321
Low temperature return
346
High temperature return
347
Electric box
357
Faulty contact (230 Vac)
A
QUADRIFOGLIO 125
/
QUADRIFOGLIO 220
780
QUADRIFOGLIO 320
900
QUADRIFOGLIO
Cure
Check the correct positioning and opera-
tion of the heating sensor
Replace the sensor
Check the wiring or replace the sensor
Replace the sensor
Check the earth connection and replace
the controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the earth connection and replace
the controller if necessary.